Z2: bypass control input/output – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 161

Advertising
background image

No.

Name

Setting Range

Default

Z1-35

Loss of Load Bypass Output Current

0.0 to 999.9

0.0 A

n

Z1-36: Loss of Load Bypass Time

While in Bypass mode, the Loss of Load detection conditions must be met for the length of time entered here before detecting

a loss of load.

No.

Name

Setting Range

Default

Z1-36

Loss of Load Bypass Time

0.0 to 300.0

1.0 s

n

Z1-37: Set Time

Changes the LCD display to time setting to set the Real Time Clock.

No.

Name

Setting Range

Default

Z1-37

Set Time

0, 1

0

Setting 0: Normal Display
Setting 1: Displays Time and Date Setting Mode

n

Z1-38: HOA Source Select

No.

Name

Setting Range

Default

Z1-38

HOA Source Select

0 to 2

0

Setting 0: Operator
Setting 1: Digital Inputs
Setting 2: Serial Communications

n

Z1-39: Drive/Bypass Source Select

No.

Name

Setting Range

Default

Z1-39

Drive/Bypass Source Select

0 to 2

0

Setting 0: Operator
Setting 1: Digital Inputs
Setting 2: Serial Communications

n

Z1-40: Auto Transfer Wait Time

If Auto Transfer is enabled and a drive fault is detected, the bypass controller will wait the length of time entered here before

switching to bypass.

No.

Name

LCD Display

Setting

Range

Default

Z1-40

Auto Transfer Wait Time

Auto Xfer Wait T

0.0 to 300.0

0.0 s

u

Z2: Bypass Control Input/Output

n

Z2-01 to Z2-08: Digital Input 1 to 8 Function Select

No.

Name

Setting Range

Default

Z2-01

Digital Input 1 Function Select

0 to 36

21

Z2-02

Digital Input 2 Function Select

0 to 36

22

Z2-03

Digital Input 3 Function Select

0 to 36

23

Z2-04

Digital Input 4 Function Select

0 to 36

24

Z2-05

Digital Input 5 Function Select

0 to 36

25

Z2-06

Digital Input 6 Function Select

0 to 36

0

Z2-07

Digital Input 7 Function Select

0 to 36

0

5.13 Z: Bypass Parameters

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

161

5

Programming