A.3 drive watt loss data – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 230

Advertising
background image

Drive Model

Normal Duty

Rated Amps (A)

<1>

Heatsink Loss (W)

Interior Unit Loss (W)

Total Loss (W)

4A0414

414

3443

1295

4738

4A0515

515

4850

1668

6518

4A0675

675

4861

2037

6898

<1> Value assumes the carrier frequency is 2 kHz (C6-02 = 1, 7, 8, 9, or A).

A.3 Drive Watt Loss Data

230

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual