E.2 European Standards

Figure E.1 CE Mark

The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in business

and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics

manufacturers, and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
Low Voltage Directive: 2006/95/EC
EMC Guidelines: 2004/108/EC
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying

the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE

standards. After setting up the device, verify that conditions meet European standards.

u

CE Low Voltage Directive Compliance

This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage

Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other

devices:

n

Area of Use

Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN 664.

n

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded

systems, contact your Yaskawa representative for instructions.

u

EMC Guidelines Compliance

This drive is tested according to European standards IEC/EN 61800-3: 2004.

n

EMC Filter Installation

Verify the following installation conditions to ensure that other devices and machinery used with this drive comply with EMC

guidelines.

1.

Move the screws to the ON position to enable the internal EMC filter.

2.

Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.

3.

Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.

Please consult Yaskawa for EMC filter installation.