Point

No.

Point

Type

Point Name

Factory

Default

(SI Units)

Engr. Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

Parameter

61

LAO

INPUT REF

2

0

HZ

0.01

0

d1-02

{62}

LAI

PID

FEEDBACK

0

PCT

0.01

0

U5-01

63

LAO

PID P GAIN

2

0.01

0

b5-02

64

LAO

PID I TIM

0.5

SEC

0.1

0

b5-03

65

LDO

PID MODE

SEL

DISABLE

1

0

ENABLE

DISABLE

b5-01

{66}

LAI

LST FLT

CODE

0

1

0

U2-02

{67}

LAI

FREF.FLT

0

HZ

0.01

0

U2-03

{68}

LAI

OUT FREQ

FLT

0

HZ

0.01

0

U2-04

{69}

LAI

OUT

CUR.FLT

0

AMPS (A)

0.01

0

U2-05

70

LAO

RD PARAM

NUM

1

1

0

71

LAI

RD PARAM

DAT

0

1

0

72

LAO

WR PARAM

NUM

1

1

0

73

LAO

WR PARAM

DAT

0

1

0

{74}

LDI

MF IN 3

MON

OFF

1

0

ON

OFF

UB-02 (Bit 4)

Bypass DI-5

{75}

LAI

OUT

VOLT.FLT

0

VOLTS (V)

0.1

0

U2-07

{76}

LAI

DC

BUS.FLT

0

VOLTS (V)

1

0

U2-08

{77}

LAI

OUT

PWR.FLT

0

KW

0.1

0

U2-09

{78}

LDI

MF IN 4

MON

OFF

1

0

ON

OFF

UB-02 (Bit 5)

Bypass DI-6

{79}

LAI

PID

DEVIATE

0

PCT

0.01

0

U5-02

80

LAO

PID I LIMIT

100

PCT

0.1

0

b5-04

81

LAO

PID UP

LIMIT

100

PCT

0.1

0

b5-06

82

LAO

PID OFFS

ADJ

100

PCT

0.1

-100

b5-07

83

LAO

PID PRI

DYTM

0

SEC

0.1

0

b5-08

84

LAO

PID FB

RMDS

0

1

0

b5-12

85

LAO

PID FB

RMDL

0

PCT

1

0

b5-13

86

LAO

PID FB

RMDT

1

SEC

0.1

0

b5-14

{87}

LAI

PID OUT

CAP

0

PCT

0.01

0

U5-14

{88}

LAI

PID REF

0

PCT

0.01

0

U5-04

{89}

LAI

COMM ERR

CD

0

1

0

U1-19

90

LDO

COMM FLT

ENA

ENABLE

1

0

ENABLE

DISABLE

Z3-11

91

LAO

CBL LOSS

FRQ

0

HZ

0.01

0

Z3-10