Remote Transfer to Bypass

Terminal TB2-4 is a programmable input with a default setting of “Remote Transfer to Bypass” operation. The function of

this terminal can be changed using parameter Z2-04.
This function allows a contact closure from a BAS, between terminals TB2-4 and TB2-10, to transfer motor operation from

Drive mode to Bypass mode. An open contact allows operation in Drive mode and a closed contact allows operation in Bypass

mode.

u

Smoke Purge Operation

Terminal TB2-5 is a programmable input with a default setting of “Smoke Purge” operation. The function of this terminal can

be changed using parameter Z2-05.
This function allows a contact closure between terminals TB2-5 and TB2-10 to transfer motor operation to bypass for smoke

purge operation. The motor overload and Safety Interlock circuit are overridden during smoke purge or in emergency fire/

smoke situations to place priority on personnel protection.

Note:

Smoke purge overrides all control inputs and bypass selector buttons. Smoke purge operation can only be terminated by opening the contact

closure at terminal TB2-5 or by opening the disconnect switch.

u

Spare Multi-Function Digital Inputs

Terminals TB2-6 and TB2-7 are spare programmable inputs. The Bypass +24 V logic circuit is interconnected with the drive

multi-function digital inputs to allow a single customer interface to control both drive and bypass circuits. The function of

these terminals can be set using parameters Z2-06 and Z2-07.

3.6 External Interlock