Z: bypass parameters, Z1: bypass control system, B.14 z: bypass parameters – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 267

Advertising
background image

B.14 Z: Bypass Parameters

u

Z1: Bypass Control System

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z1-01

(85C6) Initialize

Initialize

0: No init

1: SetAllDef

2: SetBypDef

3: SetDrvDef

8008: Pump

8009: Pump w/ PI

8010: Fan

8011: Fan w/ PI

0: No Initialize

1: Set all parameters to their default values. For drive parameters,

first issues two-wire reset, then sets individual parameter default

values.

2: Set only Bypass Controller parameters to their default values.

3: Set only Drive Controller parameters to their default values.

First issues two-wire reset, then sets individual parameter default

values.

8008: Pump

8009: Pump w/ PI

8010: Fan

8011: Fan w/ PI

Default: 0

Range: 0 to 3;

8008 to 8011

151

Z1-02

(85C7) Password

Password

Allows and restricts access to all parameters. Setting this value

equal to the value in Z1-03 toggles access to all parameter settings

except this parameter. If the value entered to Z1-02 matches the

value entered to Z1-03, the access to all parameters is denied or

granted.

Default: —

Min.: —

Max.: —

151

Z1-03

(85C8) Password Change

Pass Chg

The value entered here is the password.

Default: 0

Min.: 0

Max.: 9999

151

Z1-05

(85CA)

Auto Transfer to

Bypass Upon Drive

Fault

Auto Xfr Byp Flt

When the drive is running and a drive fault occurs, operation will

switch to Bypass mode. When the fault is cleared, operation will

switch back to Drive mode

0: Disable

1: Enable

Default: 0

Range: 0, 1

151

Z1-06

(85CB) Power-Up Mode

Power-Up

Determines the mode of the Bypass Control upon power-up.

0: OFF

1: AUTO-DRIVE

2: HAND-DRIVE

3: AUTO-BYPASS

4: HAND-BYPASS

Default: 0

Range: 0 to 4

152

Z1-07

(85CC) Speed Reference Select Spd Ref Sel

Determines the source of the Frequency Reference sent from the

Bypass Controller to the Drive.

0: Operator

1: Analog Input

2: Bypass Serial

3: Option Board (CN5)

Default: 0

Range: 0 to 3

152

Z1-08

(85CD) Run Command Select Run Cmd Sel

Determines the source of the Auto Mode Run command used by

the Bypass Controller.

0: Operator

1: Bypass Controller Digital Input

2: Bypass Serial

3: Option Board (CN5)

Default: 1

Range: 0 to 3

153

Z1-09

(85CE) HAND Mode Drive

Speed Reference

Hand Fref

This is the speed reference used when the Drive is running in

HAND mode. Units are in Hz.

Default: 10.0
Hz

<1>

Min.: 0.0

Max.: 60.0

154

B.14 Z: Bypass Parameters

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

267

B

Parameter List

Advertising