O2: hoa keypad functions, O4: maintenance monitor settings – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 142

Advertising
background image

n

o1-10: User-Set Display Units Maximum Value

Determines the display value that is equal to the maximum output frequency.

No.

Name

Setting Range

Default

o1-10

User-Set Display Units Maximum Value

1 to 60000

Determined by

o1-03

n

o1-11: User-Set Display Units Decimal Display

Determines how many decimal points should be used to set and display the frequency reference.

No.

Name

Setting Range

Default

o1-11

User-Set Display Units Decimal Display

0 to 3

Determined by

o1-03

Setting 0: No Decimal Point
Setting 1: One Decimal Point
Setting 2: Two Decimal Points
Setting 3: Three Decimal Points

u

o2: HOA Keypad Functions

These parameters determine the functions assigned to the operator keys.

n

o2-04: Drive Model Selection

Set this parameter when replacing the control board or the terminal board.

Refer to Defaults by Drive Model on page 275

for

information on drive model selection.

NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.

No.

Name

Setting Range

Default

o2-04

Drive Model Selection

-

Determined by

drive capacity

Note:

Change o2-04 setting only when necessary.

u

o4: Maintenance Monitor Settings

n

o4-03: Cooling Fan Operation Time Setting

Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03

also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after

replacing the cooling fan.

Note:

1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. “300”

will be displayed in monitor U4-03.

2. The cooling fan may require maintenance at an earlier date in harsher environments.

No.

Name

Setting Range

Default

o4-03

Cooling Fan Operation Time Setting

0 to 9999 h

0 h

5.10 o: Operator-Related Settings

142

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

Advertising