B.4 C: Tuning

C parameters are used to adjust the acceleration and deceleration times and carrier frequency selections.

u

C1: Acceleration and Deceleration Times

No.

(Addr.

Hex)

Name

Description

Values

Page

C1-01

(200)

Acceleration Time 1

Sets the time to accelerate from 0 to maximum frequency.

Default: 10.0 s

Min.: 0.0

Max.: 6000.0

103

C1-02

(201)

Deceleration Time 1

Sets the time to decelerate from maximum frequency to 0.

103

C1-09

(208)

Fast Stop Time

Sets the time for the Fast Stop function.

Default: 10.0 s

Min.: 0.0

Max.: 6000.0

103

u

C2: S-Curve Characteristics

No.

(Addr.

Hex)

Name

Description

Values

Page

C2-01

(20B)

S-Curve Characteristic at

Accel Start

The S-curve can be controlled at the four points shown below.

Run Command

Time

Output Frequency

C2-01

0.20 s <1>

C2-02

0.20 s <1>

ON

OFF

Default: 0.20 s

Min.: 0.00

Max.: 10.00

103

C2-02

(20C)

S-Curve Characteristic at

Accel End

Default: 0.20 s

Min.: 0.00

Max.: 10.00

103

<1> S-curve characteristics at decel start/end are fixed to 0.20 s.

u

C4: Torque Compensation

No.

(Addr.

Hex)

Name

Description

Values

Page

C4-01

(215)

Torque Compensation Gain

Sets the gain for the automatic torque (voltage) boost function and helps to

produce better starting torque. Used for motor 1.

Default: 1.00

Min.: 0.00

Max.: 2.50

104

u

C6: Carrier Frequency

No.

(Addr.

Hex)

Name

Description

Values

Page

C6-02

(224)

Carrier Frequency Selection

1: 2.0 kHz

2: 5.0 kHz

3: 8.0 kHz

4: 10.0 kHz

5: 12.5 kHz

6: 15.0 kHz (12.0 kHz)

7: Swing PWM1 (Audible sound 1)

8: Swing PWM2 (Audible sound 2)

9: Swing PWM3 (Audible sound 3)

A: Swing PWM4 (Audible sound 4)

Default: 7

Range: 1 to A

104

C6-05

(227)

Carrier Frequency

Proportional Gain

Determines the proportional gain for the carrier frequency.

Default:

<1>

Min.: 0

Max.: 99

105

<1> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.

B.4 C: Tuning

242