G.1 N2 Specifications and Configuration

The bypasses can be monitored and controlled by a controller on a Metasys N2 network (N2) using RS-485 technology. The

bypass act as slaves on the N2 network.
Up to 255 bypasses can communicate on a single N2 network. If more bypasses or N2 devices are required, another N2 network

is required.
The N2 node address is configurable by a parameter in the bypass. This defines the physical address of the bypass on the N2

network.
Once the addressing is set, a controller can initiate communication to the bypass. The bypass will perform the specified function

and then send a response back to the controller.

N2

Metasys Field
Controller

P1000

Bypass

P1000

Bypass

P1000

Bypass

INCHES

D

SCALE

E

I

H

F

D

C

B

A

DATE

DATE

DATE

DATE

DATE

OF YASKAWA AMERICA INC.

WITHOUT THE EXPRESS WRITTEN CONSENT

COPIED OR DISCLOSED IN WHOLE OR IN PART

IN IT ARE CONFIDENTIAL, AND CANNOT BE

THIS DOCUMENT AND INFORMATION CONTAINED

TM

-

-

-

-

-

SEE BOM

SEE NOTES

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXXXXXX

OF

XXXXXXX

Figure G.1 Connecting Multiple Bypasses to a Metasys N2 Network

N2 specifications appear in the following table:

Item

Specifications

Interface

RS-485

Communication Parameters

Communication Speed: 9600 bps

Data Length: 8-bit (fixed)

Parity: None

Stop Bit: 1-bit (fixed)

Protocol

Metasys N2

Max Number of Drives

255 per N2 Network Segment

G.1 N2 Specifications and Configuration