Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 184

Advertising
background image

The acceleration or deceleration times are too short

Calculate the torque needed during acceleration relative to the load inertia and the specified

acceleration time. If it is not possible to set the proper amount of torque, make the following changes:
• Increase the acceleration time (C1-01)
• Increase the S-curve characteristics (C2-01 and C2-02)
• Increase the capacity of the drive.

The drive is attempting to operate a specialized

motor or a motor larger than the maximum size

allowed

• Check the motor capacity.
• Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on

the motor nameplate.

Magnetic contactor (MC) on the output side of the

drive has turned on or off

Set up the operation sequence so the MC does not trip while the drive is outputting current.

V/f setting is not operating as expected

• Check the ratios between the voltage and frequency.
• Lower the voltage if it is too high relative to the frequency.

Excessive torque compensation

• Check the amount of torque compensation.
• Reduce the torque compensation gain (C4-01) until there is no speed loss and less current.

Drive fails to operate properly due to noise

interference

• Review the possible solutions provided for handling noise interference.
• Review the section on handling noise interference on page

208

and check the control circuit lines,

main circuit lines, and ground wiring.

Overexcitation gain is set too high

• Check if the fault occurs simultaneously with overexcitation function operation.
• Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain).

Run command was applied while motor was

coasting

Set b3-01 to 1 to enable Speed Search at Start.

The rated output current of the drive is too small Use a larger drive.

HOA Keypad Display

Fault Name

oFA00

Option Card Connection Error at Option Port CN5
Option compatibility error

Cause

Possible Solution

The option card installed into port CN5 is

incompatible with the drive

Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.

HOA Keypad Display

Fault Name

oH

Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02. The default value for

L8-02 is determined by drive capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high

• Check the temperature surrounding the drive. Verify temperature is within drive specifications.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy

• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-02).

External cooling fan is stopped

• Replace the cooling fan.
• After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.

HOA Keypad Display

Fault Name

oH1

Overheat 1 (Heatsink Overheat)
The heatsink temperature exceeded the drive overheat level. Overheat level is determined by drive

capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high

• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy

• Measure the output current.
• Lower the carrier frequency (C6-02).
• Reduce the load.

6.4 Fault Detection

184

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

Advertising