Z3: bypass control communication – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 164

Advertising
background image

n

Bypass Digital Output Terminal Settings

Table 5.31 Bypass Digital Output Terminal Settings

Setting

Function

0

Serial Comm Controlled

1

K1 Drive Input Contactor

2

K2 Drive Output Contactor

3

K3 Bypass Contactor

4

K4 Motor 1 Select

5

K5 Motor 2 Select

6

READY (Drive and Bypass)

7

RUN Active (Drive or Bypass)

8

Drive RUN Active

9

Bypass RUN Active

10

HAND Mode Active

11

OFF Mode Active

12

AUTO Mode Active

Setting

Function

13

Drive Mode Selected

14

Bypass Mode Selected

15

Drive or Bypass Fault Active

16

Drive Fault Active

17

Bypass Fault Active

18

Auto Transfer Active

19

Serial Run Command Active

20

Damper Actuator Output

21

ON Always

22

Loss of Load Detected

99

Not Used. This setting allows serial communications to

control the output.

u

Z3: Bypass Control Communication

n

Z3-01: Serial Communications Protocol Select

Selects the bypass serial communications protocol.

No.

Name

Setting Range

Default

Z3-01

Serial Communications Protocol Select

0, 3

3

Setting 0: Modbus
Setting 1: N2
Setting 2: P1
Setting 3: BACnet

n

Z3-02: Serial Communications Node Select

Selects the bypass serial communications node address.

Note:

Each slave must be assigned a unique slave address for serial communications to work properly. Slave addresses do not need to be assigned

in sequential order, but no two slaves may share the same address.

No.

Name

Setting Range

Default

Z3-02

Serial Communications Node Select

0 to 127

1

n

Z3-03: Serial Communications Baud Rate Select

Selects the bypass serial communications speed.

No.

Name

Setting Range

Default

Z3-03

Serial Communications Baud Rate Select

0 to 8

3

Setting 0: 1200
Setting 1: 2400
Setting 2: 4800
Setting 3: 9600
Setting 4: 19200
Setting 5: 38400
Setting 6: 57600
Setting 7: 76800
Setting 8: 115200

n

Z3-04: Serial Communications Parity Select

Selects the bypass serial communications parity. This setting is ignored when BACnet protocol is selected.

5.13 Z: Bypass Parameters

164

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual