Register No.

Contents

00CCH

Alarm Contents 6
bit 0

Output Voltage Detection Fault (VoF)

bit 1

Reserved

bit 2

Capacitor Maintenance Time (LT-3)

bit 3 to C

Reserved

bit D

Motor Underload Protection (UL6)

bit E

Waiting for Run (WrUn)

bit F

Reserved

00CDH

Reserved

00CEH

Alarm Contents 7
bit 2

Time Not Set (TIM)

bit 3

Operator Battery Low (bAT)

bit 4

Time Data Error (TdE)

bit 5

External Fan Fault (Fn1)

bit 6

Emergency Override Forward Run (EoF)

bit 7

Emergency Override Reverse Run (Eor)

00CFH

Reserved

00D0H

CPF Contents 1
bit 0, 1

Reserved

bit 2

A/D Conversion Error (CPF02)

bit 3

PWM Data Fault (CPF03)

bit 4, 5

Reserved

bit 6

EEPROM Memory Data Error (CPF06)

bit 7

Terminal Board Connection Error (CPF07)

bit 8

EEPROM Serial Communications Fault (CPF08)

bit 9 to F

Reserved

00D1H

CPF Contents 2
bit 0 to 3

Reserved

bit 4

Hardware fault at power up (CPF20)

bit 5

Hardware fault at communication start up (CPF21)

bit 6

A/D Conversion Fault (CPF22)

bit 7

PWM Feedback Fault (CPF23)

bit 8

Drive Unit Signal Fault (CPF24)

bit 9 to F

Reserved

00D2H

Reserved

00D3H to 00D7H

oFA0x Contents (CN5)

00D8H

oFA0x Contents (CN5)
bit 0

Option Compatibility Error (oFA00)

bit 1

Option not properly connected (oFA01)

bit 2 to 4

Reserved

bit 5

A/D Conversion Error (oFA05)

bit 6

Option Response Error (oFA06)

bit 7 to F

Reserved

D.9 MEMOBUS/Modbus Data Table

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

325

D