Point

No.

Point

Type

Point Name

Factory

Default

(SI Units)

Engr. Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

Parameter

92

LAO

CBL LOSS

TMR

2

SEC

0.1

0

Z3-06

{93}

LDI

OK.FAULT

OK

1

0

FAULT

OK

UB-06 (Bit 2)

{94}

LDO

RESET

FAULT

NO

1

0

RESET

NO

{95}

LDI

DRV COMM

ERR

NO FLT

1

0

FAULT

NO FLT

{96}

LDO

EXTERNAL

FLT

OK

1

0

FAULT

OK

{97}

LDI

MF IN 5

MON

OFF

1

0

ON

OFF

UB-02 (Bit 6)

Bypass DI-7

{99}

LAI

ERROR

STATUS

0

1

0

<1> For point number 35 to work properly, set Z2-02=22 Run Enable (Safety)

F.4 APOGEE FLN Point List Summary

348