Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 360

Advertising
background image

Setting 0: Ignore
Setting 1: Alarm Only
Setting 2: Fault with EF0

An EF0 fault will be sent to the drive.

Setting 3: Fault with EF0 and Open Contactors

An EF0 fault will be sent to the drive and the bypass contactor (K3) will be opened.

Setting 4: Alarm and run at preset speed set in Z3-10

Display AL14 alarm on operator.

n

Z3-06: Serial Communications Fault Time Select

Sets the time allowed to elapse since receiving serial communications before triggering a communications fault. A value of

0.0 means to never time out.

No.

Name

Setting Range

Default

Z3-06

Serial Communications Fault Detection Time

0.0 to 99.9 s

2.0 s

n

Z3-07: Serial Communications Receive to Transmit Wait Time

Sets the time to delay a serial communications response to a serial communications command.

No.

Name

Setting Range

Default

Z3-07

Serial Communications Receive to Transmit Wait Time

0 to 99 ms

5 ms

Command message

Response message

Command message

Controller→Bypass

→Bypass

Time

24-bit length Z3-07 setting

Bypass Controller

Controller

Figure G.4 Serial Communications Receive to Transmit Wait Time Setting

n

Z3-10: Cable Loss Pre-set Speed

When a serial communicaions fault is detected and Z3-05=4, the value here will become the frequency reference.

No.

Name

Setting Range

Default

Z3-10

Cable Loss Pre-set Speed

0.0 to 60.0 Hz

0.0 Hz

n

Z3-11: Serial Communication Fault Detection Selection

Enables or disables the serial communications fault detection.

No.

Name

Setting Range

Default

Z3-11

Serial Communication Fault Detection Selection

0 or 1

1

Setting 0: Disabled

No communication error detection. Ignore setting in Z3-05.

Setting 1: Enabled

If the bypass does not receive data from the master for longer than the time set to Z3-06, then a FB14 Serial Communicaions

fault will be triggered and the bypass will operate as determined by parameter Z3-05.

G.3 N2 Setup Parameters

360

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

Advertising