F: options, F6: drive/bypass communications, 6 f: options – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 114

Advertising
background image

5.6 F: Options

u

F6: Drive/Bypass Communications

n

F6-01: Communications Error Operation Selection

Determines drive operation when a communication error occurs.

No.

Parameter Name

Setting Range

Default

F6-01

Communications Error Operation Selection

0 to 3

1

Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)

Setting 1: Coast to Stop

Setting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)

Setting 3: Alarm Only (Continue Operation)

n

F6-02: External Fault from Bypass Controller Detection Selection

Determines the detection method of an external fault initiated by the bypass controller (EF0).

No.

Parameter Name

Setting Range

Default

F6-02

External Fault from Bypass Controller Detection Selection

0, 1

0

Setting 0: Always detected

Setting 1: Detection during Run only

n

F6-03: External Fault from Bypass Controller Operation Selection

Determines drive operation when an external fault is initiated by the bypass controller (EF0).

No.

Parameter Name

Setting Range

Default

F6-03

External Fault from Bypass Controller Operation Selection

0 to 3

1

Setting 0: Ramp to stop

Setting 1: Coast to stop

Setting 2: Fast Stop

Setting 3: Alarm only (continue operation)

5.6 F: Options

114

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

Advertising