Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 91

Advertising
background image

n

I Control

The output of I control is the integral of the deviation. It minimizes the offset between target and feedback value that typically

remains when pure P control is used. The integral time (I time) constant determines how fast the offset is eliminated.

n

D Control

D control predicts the deviation signal by multiplying its derivative (slope of the deviation) with a time constant, then adds

this value to the PID input. This way the D portion of a PID controller provides a braking action to the controller response and

can reduce the tendency to oscillate and overshoot.
D control tends to amplify noise on the deviation signal, which can result in control instability. Only use D control when

absolutely necessary.

n

PID Operation

To better demonstrate PID functionality,

Figure 5.11

illustrates how the PID output changes when the PID input (deviation)

jumps from 0 to a constant level.

PID input

I control

PID Output

D control

Time

PID output

Time

P control

Figure 5.11 PID Operation

n

Using PID Control

Applications for PID control are listed in

Table 5.2

.

Table 5.2 Using PID Control

Application

Description

Sensors Used

Speed Control

Machinery speed is fed back and adjusted to meet the target value. Synchronous control is

performed using speed data from other machinery as the target value

Tachometer

Pressure

Maintains constant pressure using pressure feedback.

Pressure sensor

Fluid Control

Keeps flow at a constant level by feeding back flow data.

Flow rate sensor

Temperature

Control

Maintains a constant temperature by controlling a fan with a thermostat.

Thermocoupler,

Thermistor

n

PID Setpoint Input Methods

The PID setpoint input depends on the PID function setting in parameter b5-01.
If parameter b5-01 is set to 1 or 2, the frequency reference source in b1-01 (or b1-15) or one of the inputs listed in

Table 5.3

becomes the PID setpoint.
If b5-01 is set to 3 or 4, then the PID setpoint can be input from one of the sources listed in

Table 5.3

.

Table 5.3 PID Setpoint Sources

PID Setpoint Source

Settings

Analog Input A1

Set H3-02 = C

Analog Input A2

Set H3-10 = C

Analog Input A3

Set H3-06 = C

MEMOBUS/Modbus Register 0006 H

Set bit 1 in register 000F H to 1 and input the setpoint to register 0006 H

Pulse Input RP

Set H6-01 = 2

5.2 b: Application

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

91

5

Programming

Advertising