B.15 defaults by drive model – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 284

Advertising
background image

No.

Name

Unit

Default Settings

Drive Model

4A0165

4A0208

4A0250

Bypass Model

B156

B180

B240

o2-04

Drive Model Selection

Hex.

A5

A6

A7

E2-11

Motor rated power

kW (HP)

90

(125)

110

(150)

132

(200)

b3-04

V/f Gain during Speed Search

%

60

60

60

b3-06

Output Current 1 during Speed Search

0.7

0.7

0.7

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

2.00

2.00

2.00

b8-04

Energy Saving Coefficient Value

38.91

36.23

32.79

C5-17

Motor Inertia

kgm

2

1.10

1.90

2.10

C6-02

Carrier Frequency Selection

7

7

7

E2-01

Motor Rated Current

A

156

190

223

E2-02

Motor Rated Slip

Hz

1.4

1.4

1.38

E2-03

Motor No-Load Current

A

40

49

58

E2-05

Motor Line-to-Line Resistance

Ω

0.056

0.046

0.035

E2-06

Motor Leakage Inductance

%

20

20

20

E2-10

Motor Iron Loss for Torque Compensation

W

1760

2150

2350

L2-02

Momentary Power Loss Ride-Thru Time

s

2

2

2

L2-03

Momentary Power Loss Min. Basebl. Time

s

1.5

1.7

1.7

L2-04

Momentary Power Loss Volt. Recov. Time

s

1

1

1

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.592

0.646

0.673

L8-02

Overheat Alarm Level

°C

130

120

120

L8-35

Installation Method Selection

0

0

0

L8-38

Carrier Frequency Reduction Selection

2

2

2

n1-03

Hunting Prevention Time Constant

ms

30

30

30

B.15 Defaults by Drive Model

284

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual