Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 268

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z1-10

(85CF) Smoke Purge Preset

Frequency Reference

Smoke Purge

Sets the speed at which the drive will run when the Smoke Purge

Drive input is active.

Default: 60.0
Hz

<1>

Min.: 0.0

Max.: 60.0

154

Z1-11

(85D0) 2-Motor AND/OR

Function Select

2-Mtr AND/OR Sel

0: Disabled (ignore digital inputs)

1: Always use only motor 1

2: Always use only motor 2

3: Always use motors 1 AND 2

4: OR function motor selected by digital input in HAND and

AUTO modes

5: OR function use motor 1 in HAND mode and motor selected

by digital input in AUTO mode

6: OR function use motor 2 in HAND mode and motor selected

by digital input in AUTO mode

7: AND/OR function motor selected (1, 2, or both) by (2) digital

inputs in HAND and AUTO mode

8: AND/OR function use motor 1 in HAND mode and motor

selected (1, 2, or both) by (2) digital inputs in AUTO mode

9: AND/OR function use motor 2 in HAND mode and motor

selected (1, 2, or both) by (2) digital inputs in AUTO mode

10: AND/OR function use motors 1 AND 2 in HAND mode and

motor selected (1, 2, or both) by (2) digital inputs in AUTO mode

Default: 0

Range: 0 to 10

154

Z1-12

(85D1) Run Delay Time

Run Delay Time

Delays the drive or bypass Run from when commanded (after

RUN, RUN ENABLE, and RUN INTERLOCK are all asserted).

Default: 0.0 s

Min.: 0.0

Max.: 300.0

154

Z1-13

(85D2) Pre-Interlock Run

Select

Pre Int Run Sel

Allows running at a preset speed starting immediately upon a Run

command, ignoring the BAS Interlock Input. The drive frequency

reference stays at this preset speed until the Run Delay time

(Z1-12) times out.

0: Disabled

1: Enable delay time only

Default: 0

Range: 0, 1

154

Z1-14

(85D3) Run Delay Frequency

Reference

Run Delay Fref

Frequency used while delaying the Run command.

Default: 60.0
Hz

<1>

Min.: 0.0

Max.: 60.0

155

Z1-15

(85D4) Interlock Wait Time

Interlck Wait

Upon entering a Run command, the damper actuator output will

be asserted. When an input is programmed for Interlock and the

time set to this parameter is reached before the Interlock input

goes active, a fault will be declared.

A setting of 0.0 will never time out.

Default: 0.0 s

Min.: 0.0

Max.: 300.0

155

Z1-16

(85D5)

Energy Savings Mode

Enable

Enrgy Savings En

0: Disable

1: Enable (Freq)

2: Enable (Freq + Cur)

Note:

Energy Savings will not function if the motor is

running in reverse.

Default: 0

Range: 0 to 2

158

Z1-17

(85D6) Energy Savings Mode

Frequency

Energy Freq

Sets the value of the drive frequency reference for use in

comparison to enter or exit Energy Savings mode.

Default: 60.0
Hz

<1>

Min.: 0.0

Max.: 60.0

158

Z1-18

(85D7) Energy Savings Mode

Output Current Level

Energy Iout Lvl

Allows system to switch when the output current rises above this

level of motor rated current for time specified in Energy Time.

Default: 0.0%

Min.: 0.0

Max.: 100.0

158

Z1-19

(85D8)

Energy Savings Mode

Frequency Reference

Deadband

Enrgy Fref Dbnd

Sets the tolerance around the drive frequency reference value

during comparisons to enter or exit Energy Savings mode

Default: 0.5 Hz

<1>

Min.: 0.0

Max.: 5.0

159

Z1-20

(85D9)

Energy Savings Mode

Output Frequency

Deadband

Energy Freq Dbnd

Sets the tolerance around the drive output frequency value during

comparisons to enter or exit Energy Savings mode.

Default: 0.5 Hz

<1>

Min.: 0.0

Max.: 5.0

159

Z1-21

(85DA)

Energy Savings Mode

Output Current

Deadband

Energy Iout Dbnd

Sets the tolerance around the drive output current value during

comparisons to enter or exit Energy Savings mode as a percentage

of motor rated current.

Default: 15.0%

Min.: 0.0

Max.: 30.0

159

B.14 Z: Bypass Parameters

268

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual