Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 321

Advertising
background image

Register No.

Contents

002DH

Output Terminal Status
bit 0

Multi-Function Contact Output 1 (terminal MD-ME-MF)

bit 1

Multi-Function Contact Output 2 (terminal M1-M2)

bit 2

Multi-Function Contact Output 3 (terminal M3-M4)

bit 3 to 6

Reserved

bit 7

Fault Contact Output (terminal MA/MB-MC)

bit 8 to F

Reserved

002EH

Reserved

002FH

Frequency Reference Bias (from Up/Down 2 Function), 0.1% units

0030H

Reserved

0031H

DC Bus Voltage, 1 Vdc units

0032H, 0033H

Reserved

0034H

Product Code 1 [ASCII], Product Type

0035H

Product Code 2 [ASCII], Region Code

0036H, 0037H

Reserved

0038H

PI Feedback, 0.1% units, unsigned, 100% / max. output frequency

0039H

PI Input, 0.1% units, signed, 100% / max. output frequency

003AH

PI Output, 0.1% units, signed, 100% / max. output frequency

003BH, 003CH

Reserved

003DH

Communications Error Contents

<2>

bit 0

CRC Error

bit 1

Data Length Error

bit 2

Reserved

bit 3

Parity Error

bit 4

Overrun Error

bit 5

Framing Error

bit 6

Timeout

bit 7 to F

Reserved

003EH

Output Frequency

r/min

<4>

003FH

0.01% units

0040H to 004AH

Used for various monitors U1-oo.

Refer to U: Monitors on page 259

for parameter details.

004BH

Drive status (U1-12)
bit 0

During Run

bit 1

During Zero Speed

bit 2

During Reverse Run

bit 3

During Fault Reset Signal Input

bit 4

During Speed Agree

bit 5

Drive Ready

bit 6

Alarm

bit 7

Fault

bit 8

During Operation Error (oPEoo)

bit 9

During Momentary Power Loss

bit A, bit B

Reserved

bit E

ComRef status, NetRef status

bit F

ComCtrl status, NetCtrl status

004CH to 007EH

Used for various monitors U1-oo, U4-oo, U5-oo and U6-oo.

Refer to U: Monitors on page 259

for parameter details.

007FH

Alarm Code,

Refer to Alarm Register Contents on page 330

for alarm codes.

0080H to 0097H

Used for monitors U2-oo, U3-oo.

Refer to U: Monitors on page 259

for parameter details and

Refer to Fault Trace

Contents on page 328

for register value descriptions.

0098H

High Word of Accumulated Operation Time Monitor, 10 h units (U4-01)

D.9 MEMOBUS/Modbus Data Table

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

321

D

MEMOBUS/Modbus Communications

Advertising