A.1 Power Ratings

u

Three-Phase 208 Vac Bypass Drive Models D002 to D030

Table A.1 Power Ratings (Three-Phase 208 Vac)

Item

Specification

Bypass Model P1Bo

D002

D003

D004

D007

D010

D016

D024

D030

Maximum Applicable

Motor Capacity (HP)

<1>

0.5

0.75

1

2

3

5

7.5

10

Input

Input Current Range (A)

<2>

2.7

to 4.6

3.9

to 5.8

5.6

to 7.5

8.3

to 10.2

12.3

to 14.2

17.7

to 19.6

29.8

to 31.5

40.0

to 41.7

Rated Voltage

Rated Frequency

Three-phase 208 Vac 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency

Fluctuation

±5%

Output

Rated Output Current (A)

2.4

3.5

4.6

7.5

10.6

16.7

24.2

30.8

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

<3>

User-adjustable between 2 and 15 kHz

Maximum Output Voltage (V)

Three-phase 208 Vac

Maximum Output Frequency

(Hz)

400 Hz (user-set)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.

<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.

u

Three-Phase 208 Vac Bypass Drive Models D046 to D211

Table A.2 Power Ratings (Three-Phase 208 Vac)

Item

Specification

Bypass Model P1Bo

D046

D059

D074

D088

D114

D143

D169

D211

Maximum Applicable

Motor Capacity (HP)

<1>

15

20

25

30

40

50

60

75

Input

Input Current Range (A)

<2>

56.1

to 57.8

68.9

to 70.6

89.4

to 90.3

89.5

to 92.4

113.1

to 116.0

140.2

to 142.4

165.4

to 167.6

201.4

to 203.6

Rated Voltage

Rated Frequency

Three-phase 208 Vac 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency

Fluctuation

±5%

Output

Rated Output Current (A)

46.2

59.4

74.8

88.0

114

143

169

211

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

<3>

User-adjustable between 2 and 15 kHz

User-adjustable between

2 and 10 kHz

Maximum Output Voltage (V)

Three-phase 208 Vac

Maximum Output Frequency

(Hz)

400 Hz (user-set)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.

<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.

A.1 Power Ratings

224

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual