5 start-up procedure, Press – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 73

Advertising
background image

Step

Display/Result

Motor Rotation in Drive Mode

1. Press

HAND

to give the drive a Run command from HAND mode. The HAND light will

turn on and the motor will rotate at the value set to parameter Z1-09 (10 Hz default).

F2

F1

ESC

M

M

AUTO

OFF

ENTER

RESET

ALM

DIGITAL OPERATOR JVOP-183

HAND

ENTER

Off

On

HAND

HAND

DRV-OFF

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

Freq Ref (AUTO)

BYPASS

LSEQ

LREF

2. Ensure the motor is rotating in the correct direction and that no faults or alarms occur.

Motor

Forward

3.

If the direction of motor rotation is incorrect, press

OFF

to stop the motor. The HAND

light turns OFF and the motor coasts to stop.

Skip to step 6 If the direction of motor rotation is correct.

F2

F1

ESC

M

M

AUTO

OFF

ENTER

RESET

ALM

DIGITAL OPERATOR JVOP-183

HAND

On

Off

HAND

HAND

DRV-OFF

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

Freq Ref (AUTO)

BYPASS

LSEQ

LREF

4.

Turn off the power to the P1000 Bypass.

WARNING! Electrical Shock Hazard. Do not touch any terminals before the

capacitors have fully discharged. Failure to comply could result in death or serious

injury. Before servicing, disconnect all power to the equipment. The internal

capacitor remains charged even after the power supply is turned off. The charge

indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent

electric shock, wait for at least the time specified on the warning label, once all

indicators are OFF, measure for unsafe voltages to confirm the drive is safe prior

to servicing.

Switch the wires for T1 and T2 on the output terminals of the motor overload relay. Re-

tighten the terminal lugs and reapply power.

5. Reapply the power, press

HAND

and re-check the rotation direction.

6. Verify that the system is ready to operate at full speed by making sure that the building

automation system logic is ready for the start, stop, and speed command functions.

7.

Press

to increase the frequency reference in increments of 10 Hz, verifying smooth

operation at all speeds. For each frequency, check the drive output current using monitor

U1-03. The current should be well below the motor rated current.

DRV-RUN DRIVE

U1-01=

0

010.0Hz

(0.0-60.0)

“10.0Hz”

Frequency Ref

8. Press

F1

,

F2

, or

to navigate the cursor through the numerical positions. Use

and

to change the value of the selected numerical place.

9. Press

to confirm the new frequency reference; the drive will begin to accelerate or

decelerate.

10.

Check the motor current using U1-03 then measure the output voltage (Line-to-Line and

Line-to-Ground) using a multimeter and record the values for future reference.

Press

OFF

to stop the motor.

DRV-RUN DRIVE

U

1

-03=

0

2.5A

Monitor

U1-04= 0
U1-06= 0.0VAC

LSEQ

LREF

RLY

DRV/BYP

4.5 Start-Up Procedure

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

73