Figure 5.40, Sequence timer example 2, 11 s: special parameters – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 147

Advertising
background image

Mon

Tue

Wed

Thur

Fri

Sat

Sun

0:00
1:00
2:00
3:00
4:00
5:00
6:00

Sequence Timer 3

Run at d1-03

7:00
8:00
9:00

10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00

Sequence Timer 4

18:00
19:00

Activate Sequence

20:00

Timer 4 digital output

21:00
22:00
23:00

Sequence Timer 1

Run at d1-01

Sequence Timer 2

Run at d1-02 with PI control disabled

Figure 5.40 Sequence Timer Example 1

n

Sequence Timer Example 2

Set the parameters as shown in

Table 5.25

to accomplish the timer sequencing in

Figure 5.41

.

Table 5.25 Sequence Timer Example 2 Parameter Settings

No.

Name

Setting

Comment

S2-01

Sequence Timer 1 Start Time

00:00

S2-02

Sequence Timer 1 Stop Time

24:00

S2-03

Sequence Timer 1 Day Selection

2

Mon to Fri

S2-04

Sequence Timer 1 Selection

1

Run

S2-05

Sequence Timer 1 Reference Source

0

Operator (d1-01)

S2-06

Sequence Timer 2 Start Time

06:00

S2-07

Sequence Timer 2 Stop Time

06:00

S2-08

Sequence Timer 2 Day Selection

3

Sat to Sun

S2-09

Sequence Timer 2 Selection

1

Run

S2-10

Sequence Timer 2 Reference Source

2

Operator (d1-03)

S2-11

Sequence Timer 3 Start Time

0:00

n/a

S2-12

Sequence Timer 3 Stop Time

0:00

n/a

S2-13

Sequence Timer 3 Day Selection

0

Timer Disabled

S2-14

Sequence Timer 3 Selection

0

n/a

S2-15

Sequence Timer 3 Reference Source

0

n/a

S2-16

Sequence Timer 4 Start Time

00:00

n/a

S2-17

Sequence Timer 4 Stop Time

00:00

n/a

S2-18

Sequence Timer 4 Day Selection

0

Timer Disabled

S2-19

Sequence Timer 4 Selection

0

n/a

S2-20

Sequence Timer 4 Reference Source

0

n/a

5.11 S: Special Parameters

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

147

5

Programming