No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S2-17

(3216)

Sequence Timer 4 Stop

Time

Tmr 4 Stop Time

Sets the stop time for timer 4. The value must be set greater than

or equal to S2-16.

Default: 00:00

Min.: 00:00

Max.: 24:00

145

S2-18

(3217)

Sequence Timer 4 Day

Selection

Tmr 4 Day Sel

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Sets the days for which sequence timer 4 is active.

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Default: 0

Range: 0 to 10

145

S2-19

(3218)

Sequence Timer 4

Selection

Tmr 4 Seq Sel

0: Digital out only

1: Run

2: Run - PI Disable

Sets the action that occurs when sequence timer 4 is active.

0: Digital output only

1: Run

2: Run - PI disable

Default: 0

Range: 0 to 2

145

S2-20

(3219)

Sequence Timer 4

Reference Source

Tmr 4 Ref Source

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial com

7: Pulse input

Selects the frequency reference source used for running the drive

when sequence timer 1 is active (only applicable when S2-04 is

set to 1 or 2).

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial communication

7: Pulse input

Default: 0

Range: 0 to 5; 7

146

u

T: Motor Tuning

Enter data into the following parameters to tune the motor and drive for optimal performance. When the drive is not accessible,

the current values of these parameters are not accessible. The default values are set by the Bypass Controller when a Bypass

Control Parameter Initialize (Z1-01 = 1, 2, or 3) command is given.

u

T1: Induction Motor Auto-Tuning

No.

(Addr.

Hex)

Name

Description

Values

Page

T1-00

(0700)

Motor 1/Motor 2 Selection

1: Motor 1

2: Motor 2

Default: 1

Range: 1, 2

79

T1-01

(0701)

<1>

Auto-Tuning Mode

Selection

2: Stationary Auto-Tuning for Line-to-Line Resistance

3: Rotational Auto-Tuning for V/f Control Energy Saving

Default: 2

Range: 2, 3

79

T1-02

(0702)

Motor Rated Power

Sets the motor rated power as specified on the motor nameplate.

Note:

Use the following formula to convert horsepower into kilowatts:

1HP = 0.746 kW.

Default:

<2>

Min.: 0.00 kW

Max.: 650.00 kW

79

T1-03

(0703)

Motor Rated Voltage

Sets the motor rated voltage as specified on the motor nameplate.

Default: 200.0 V

<3>

Min: 0.0
Max: 255.0

<3>

79

T1-04

(0704)

Motor Rated Current

Sets the motor rated current as specified on the motor nameplate.

Default:

<2>

Min.: 10% of drive

rated current

Max.: 200% of

drive rated current

80

T1-05

(0705)

Motor Base Frequency

Sets the rated frequency of the motor as specified on the motor nameplate.

Default: 60.0 Hz

Min.: 0.0

Max.: 240.0

80

T1-06

(0706)

Number of Motor Poles

Sets the number of motor poles as specified on the motor nameplate.

Default: 4

Min.: 2

Max.: 48

80