V/f pattern settings e1-05, 5 e: motor parameters, Setting a custom v/f pattern (setting f: default) – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 112

Advertising
background image

Predefined V/f Patterns for Models D273 to D396 and B124 to B590

The voltage values in the graphs for settings 0 to E apply to applications with 200 V motors. Double the voltage values for

400 V motors. The voltage values in settings 0 to E do not apply to 208, 230, or 460 V motor applications.

Table 5.18 Rated Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

6

200

1.3 2.5

50

12

V

oltage (V)

Frequency (Hz)

0

6

200

1.5 3

60

12

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 5.19 Variable Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

5

200

1.3

25

50

35

V

oltage (V)

Frequency (Hz)

0

6

200

1.3

25

50

50

V

oltage (V)

Frequency (Hz)

0

5

200

1.5

30

60

35

V

oltage (V)

Frequency (Hz)

0

6

200

1.5

30

60

50

V

oltage (V)

Frequency (Hz)

Table 5.20 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

7

200

1.3 2.5

50

15

V

oltage (V)

Frequency (Hz)

0

9

200

1.3 2.5

50

20

V

oltage (V)

Frequency (Hz)

0

7

200

1.5 3

60

15

V

oltage (V)

Frequency (Hz)

0

11

200

1.5 3

60

20

V

oltage (V)

Frequency (Hz)

Table 5.21 Constant Output, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

6

12

200

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

6.9

230

1.5 3

60

13.8

V

oltage (V)

Frequency (Hz)

Setting a Custom V/f Pattern (Setting F: Default)

Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameter E1-05.

n

V/f Pattern Settings E1-05

If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the maximum voltage in parameters

E1-05. To create a new V/f pattern, set E1-03 to F.

No.

Parameter Name

Setting Range

Default

E1-05

Maximum Voltage

0.0 to 510.0 V

<1>

<2>

<1> Values shown are specific to 480 Vac.
<2> Default setting is determined by parameter E1-03, V/f Pattern Selection.

5.5 E: Motor Parameters

112

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual