General description, Control mode details, 2 general description – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 27

Advertising
background image

1.2 General Description

u

Control Mode Details

Table 1.1

gives an overview of the various features associated with the P1000 Bypass.

Table 1.1 Control Mode Features

Motor Type

Induction Motors

Comments

Control Mode

V/f

Basic Description

V/f control

Type of Applications

Motor Type

IM

Multi Motor

YES

Motor data unknown

YES

High Speed Accuracy

Control Characteristics

Speed Control Range

1:40

May fluctuate with characteristics and motor temperature.

Speed Accuracy

±2 to 3%

Speed deviation when operating at constant speed may fluctuate
with characteristics and motor temperature.

Speed Response

3 Hz (approx.)

Max. frequency of a speed reference signal that the drive can follow
may fluctuate with characteristics and motor temperature.

Starting Torque

140% at 3 Hz

Starting torque may fluctuate with characteristics and motor
temperature.
Performance may differ by capacity.

Application-Specific

Speed Search

YES

Bi-directional speed detection of a coasting motor to restart it
without stopping.

Energy-Saving Control

YES

Saves energy by always operating the motor at its maximum
efficiency.

High Slip Braking

YES

Increases motor loss to allow for faster deceleration. Effectiveness
may vary based on motor characteristics.

Kinetic Energy Buffering

YES

Decelerates the drive to allow it to ride through a momentary power
loss and continue operation.

Overexcitation Deceleration

YES

Provides fast deceleration without using a braking resistor.

Overvoltage Suppression

YES

Prevents overvoltage by increasing speed during regeneration.

1.2 General Description

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

27

1

Receiving

Advertising