H3: multi-function analog inputs – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 247

Advertising
background image

u

H3: Multi-Function Analog Inputs

No.

(Addr.

Hex)

Name

Description

Values

Page

H3-01

(410)

Terminal A1 Signal Level

Selection

0: 0 to 10 V with zero limit

1: 0 to 10 V without zero limit

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use jumper switch S1 to set input terminal A1 for current or

voltage.

Default: 0

Range: 0 to 3

117

H3-02

(434)

Terminal A1 Function

Selection

Sets the function of terminal A1.

Default: 0

Range: 0 to 26

118

H3-03

(411)

Terminal A1 Gain Setting

Sets the level of the input value selected in H3-02 when 10 V is input at

terminal A1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

118

H3-04

(412)

Terminal A1 Bias Setting

Sets the level of the input value selected in H3-02 when 0 V is input at terminal

A1.

Default: 0.0%

Min.: -999.9

Max.: 999.9

118

H3-05

(413)

Terminal A3 Signal Level

Selection

0: 0 to 10 V with zero limit

1: 0 to 10 V without zero limit

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use Jumper S1 to set input terminal A3 for a current or voltage

input signal.

Default: 0

Range: 0 to 3

119

H3-06

(414)

Terminal A3 Function

Selection

Sets the function of terminal A3.

Default: 2

Range: 0 to 26

119

H3-07

(415)

Terminal A3 Gain Setting

Sets the level of the input value selected in H3-06 when 10 V is input at

terminal A3.

Default: 100.0%

Min.: -999.9

Max.: 999.9

119

H3-08

(416)

Terminal A3 Bias Setting

Sets the level of the input value selected in H3-06 when 0 V is input at terminal

A3.

Default: 0.0%

Min.: -999.9

Max.: 999.9

119

H3-09

(417)

Terminal A2 Signal Level

Selection

0: 0 to 10 V with zero limit

1: 0 to 10 V without zero limit

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use jumper switch S1 to set input terminal A2 for current or

voltage input signal.

Default: 2

Range: 0 to 3

119

H3-10

(418)

Terminal A2 Function

Selection

Sets the function of terminal A2.

Default: 0

Range: 0 to 26

119

H3-11

(419)

Terminal A2 Gain Setting

Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input

at terminal A2.

Default: 100.0%

Min.: -999.9

Max.: 999.9

120

H3-12

(41A)

Terminal A2 Bias Setting

Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is

input at terminal A2.

Default: 0.0%

Min.: -999.9

Max.: 999.9

120

H3-13

(41B)

A1/A2 Input Filter Time

Constant

Sets a primary delay filter time constant for terminals A1 and A2. Used for

noise filtering.

Default: 0.03 s

Min.: 0.00

Max.: 2.00

120

H3-14

(41C)

Analog Input Terminal

Enable Selection

Determines which analog input terminals will be enabled when a digital input

programmed for “Analog input enable” (H1-oo = C) is activated.

1: Terminal A1 only

2: Terminal A2 only

3: Terminals A1 and A2 only

4: Terminal A3 only

5: Terminals A1 and A3

6: Terminals A2 and A3

7: All terminals enabled

Default: 7

Range: 1 to 7

120

H3-16

(2F0)

Terminal A1 Offset

Adds an offset when the analog signal to terminal A1 is at 0 V.

Default: 0

Min.: -500

Max.: 500

121

B.8 H Parameters: Multi-Function Terminals

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

247

B

Parameter List