B.9 L: Protection Function

L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,

frequency detection, fault restarts, overtorque detection, and other types of hardware protection.

u

L1: Motor Protection

No.

(Addr.

Hex)

Name

Description

Values

Page

L1-01

(480)

Motor Overload Protection

Selection

0: Disabled

1: General purpose motor (standard fan cooled)

The drive may not be able to provide protection when using multiple motors,

even if overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal

relays to each motor.

Default: 1

Range: 0, 1

126

L1-02

(481)

Motor Overload Protection

Time

Sets the motor thermal overload protection (oL1) time.

Default: 1.0 min

Min.: 0.1

Max.: 5.0

127

u

L2: Momentary Power Loss Ride-Thru

No.

(Addr.

Hex)

Name

Description

Values

Page

L2-01

(485)

Momentary Power Loss

Operation Selection

0: Disabled.

Drive trips on Uv1 fault when power is lost.

1: Recover within the time set in L2-02.

Uv1 will be detected if power loss is longer than L2-02.

Note:

L2-02 is dependent on drive model selection and is not

accessible.

2: Recover as long as CPU has power.

Uv1 is not detected.

Default: 2

Range: 0 to 2

127

L2-02

(486)

Momentary Power Loss

Ride-Thru Time

Sets the Power Loss Ride-Thru time. Enabled only when L2-01 = 1 or 3.

Default:

<1>

Min.: 0.0 s

Max.: 25.5 s

128

L2-03

(487)

Momentary Power Loss

Minimum Baseblock Time

Sets the minimum wait time for residual motor voltage decay before the drive

output reenergizes after performing Power Loss Ride-Thru.

Increasing the time set to L2-03 may help if overcurrent or overvoltage occur

during Speed Search or during DC Injection Braking.

Default:

<1>

Min.: 0.1 s

Max.: 5.0 s

128

L2-05

(489)

Undervoltage Detection

Level (Uv1)

Sets the DC bus undervoltage trip level.

Default: 190 Vdc

<2> <3>

Min.: 150 Vdc
Max.: 220 Vdc

<3>

128

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameters o2-04, Drive Model Selection, and E1-01, Input Voltage Setting.
<3> Values shown are specific to 208 V bypass drives. Double the value for 480 V bypass drives.

u

L3: Stall Prevention

No.

(Addr.

Hex)

Name

Description

Values

Page

L3-02

(490)

Stall Prevention Level

during Acceleration

Used when L3-01 = 1 or 2. 100% is equal to the drive rated current.

Default: 120%

Min.: 0
Max.: 120

<1>

128

L3-03

(491)

Stall Prevention Limit

during Acceleration

Sets Stall Prevention lower limit during acceleration when operating in the

constant power range. Set as a percentage of drive rated current.

Default: 50%

Min.: 0

Max.: 100

129

B.9 L: Protection Function

250