L2: momentary power loss ride-thru, Refer to l2-01 – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 127

Advertising
background image

n

L1-02: Motor Overload Protection Time

Sets the time for the drive to shut down on motor overload (oL1) when the motor is running with excessive current. Enter the

time the motor can withstand operating at 150% current after previously running at 100% current (hot motor overload

condition). This parameter rarely requires adjustment.

No.

Name

Setting Range

Default

L1-02

Motor Overload Protection Time

0.1 to 5.0 minutes

1.0 minutes

Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start after continuous operation

at 100%.

Figure 5.31

illustrates an example of the electrothermal protection operation time using a general-purpose motor operating at

the value of E1-06, Motor Base Speed, with L1-02 set to one minute.
Motor overload protection operates in the area between a cold start and a hot start.
• Cold start: Characteristics of motor protection operation time in response to an overload situation that was suddenly reached

when starting a stationary motor.

• Hot start: Characteristics of motor protection operation time in response to an overload situation that occurred while the

motor was operating continuously at or below its rated current.

Operation time (minutes)

Cold start
(characteristics when an
overload occurs at a
complete stop)

Hot start
(characteristics when an
overload occurs during
continuous operation at 100%)

Motor current (%)

E2-01 = 100% motor current

10

7

3

1

0.4

0.1

0

100

150

200

Figure 5.31 Protection Operation Time for General Purpose Motors at the Rated Output Frequency

u

L2: Momentary Power Loss Ride-Thru

n

L2-01: Momentary Power Loss Operation Selection

When a momentary power loss occurs (DC bus voltage falls below the level set in L2-05), the drive can automatically return

to the operation it was performing prior to the power loss based on certain conditions.

No.

Name

Setting Range

Default

L2-01

Momentary Power Loss Operation Selection

0 to 2

2

Setting 0: Disabled

If power is not restored within 15 ms, a Uv1 fault will result and the motor coasts to stop.

Setting 1: Recover within L2-02

When a momentary power loss occurs, the drive output will be shut off. If the power returns within the time set to parameter

L2-02, the drive will perform Speed Search and attempt to resume operation. If the power does not return within this time, it

will trigger a Uv1 fault.

Note:

L2-02 value is dependent on drive model selection and is not accessible.

Setting 2: Recover as long as CPU Has Power

When a momentary power loss occurs, the drive output will be shut off. If the power returns and the drive control circuit has

power, the drive will attempt to perform Speed Search and resume the operation. This will not trigger a Uv1 fault.

Notes on Settings 1 and 2

• “Uv” will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is not

output at this time.

5.8 L: Protection Functions

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

127

5

Programming