Mechanical installation, Installation environment, 2 mechanical installation – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 38

Advertising
background image

2.2 Mechanical Installation

This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.

u

Installation Environment

Install the P1000 Bypass in an environment matching the conditions below to prolong its optimum performance life.
Move the disconnect handle into the OFF position to open the enclosure door for all bypass units. The wall mount units have

two full-turn fasteners, CCW to open, that require a flat blade screwdriver to open the enclosure door.
Wall mount units require a minimum 6 inch clearance above and below and a 3 inch clearance to the left to achieve adequate

heatsink cooling.

Table 2.1 Installation Environment

Environment

Conditions

Installation Area

Indoors

Ambient Temperature

-10 °C to +40 °C

Drive reliability improves in environments without wide temperature fluctuations.

Humidity

95% RH or less and free of condensation

Storage Temperature

-20 to +60 °C

Surrounding Area

Install the bypass in an area free from:
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides

Altitude

1000 m or lower, up to 3000 m with derating.

Refer to Drive Derating Data on page 231

for details.

Vibration

10 to 20 Hz at 3.24 m/s

2

(10.6 ft/s

2

)

20 to 55 Hz at 2.16 m/s

2

(7.1 ft/s

2

)

Orientation

Install the bypass vertically to maintain maximum cooling effects.

NOTICE: Avoid placing peripheral devices, transformers, or other electronics near the P1000 Bypass as the noise created can lead to

erroneous operation. If such devices must be used in close proximity to the Bypass, take proper steps to shield the bypass from noise.

NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the P1000 Bypass during installation. Failure

to comply could result in damage to the bypass. Place a temporary cover over the top of the drive during installation. Remove the temporary

cover before bypass start-up, as the cover will reduce ventilation and cause the Bypass to overheat.

2.2 Mechanical Installation