PID feedback value

PID

Feedback

Detection

Loss Level

(b5-13)

PID Feedback

Loss Detection Time

(b5-14)

no FbL
detection

FbL detection

time

PID Feedback

Loss Detection Time

(b5-14)

Figure 5.13 PID Feedback Loss Detection

n

b5-12: PID Feedback Loss Detection Selection

Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.

No.

Parameter Name

Setting Range

Default

b5-12

PID Feedback Loss Detection Selection

0 to 5

0

Setting 0: Digital Output Only

A digital output set for “PID feedback low” (H2-oo = 3E) will be triggered if the PID feedback value is below the detection

level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PID feedback high” (H2-oo = 3F) will be

triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a

fault nor an alarm is displayed on the digital operator and the drive will continue operation. The output resets when the feedback

value leaves the loss detection range.

Setting 1: Feedback Loss Alarm

If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low”

alarm will be displayed and a digital output set for “PID feedback low” (H2-oo = 3E) will be triggered. If the PID feedback

value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed

and a digital output set for “PID feedback high” (H2-oo = 3F) will be triggered. Both events trigger an alarm output

(H1-oo = 10). The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection

range.

Setting 2: Feedback Loss Fault

If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FbL - Feedback Low”

fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FbH

- Feedback High” fault will be displayed. Both events trigger a fault output (H1-oo = E) and cause the drive to stop the

motor.

Setting 3: Digital Output Only, even if PID Is Disabled by Digital Input

Same as b5-12 = 0. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

Setting 4: Feedback Loss Alarm, even if PID Is Disabled by Digital Input

Same as b5-12 = 1. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

Setting 5: Feedback Loss fault, even if PID Is Disabled by Digital Input

Same as b5-12 = 2. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

n

b5-13: PID Feedback Low Detection Level

Sets the feedback level used for PID feedback low detection. The PID feedback must fall below this level for longer than the

time set to b5-14 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-13

PID Feedback Low Detection Level

0 to 100%

0%

n

b5-14: PID Feedback Low Detection Time

Sets the time that the PID feedback has to fall below b5-13 before feedback loss is detected.

5.2 b: Application