Table 5.6 PID Fine Tuning

Goal

Tuning Procedure

Result

Suppress overshoot

• Reduce the derivative time (b5-05)
• Increase the integral time (b5-03)

Response

Before adjustment

After adjustment

Time

Achieve stability quickly while

allowing some overshoot

• Decrease the integral time (b5-03)
• Increase the derivative time (b5-05)

Response

Before adjustment

After adjustment

Time

Suppress long cycle oscillations

(longer than the integral time setting) Increase the integral time (b5-03)

Response

Before adjustment

After adjustment

Time

Suppress short cycle oscillations

• If oscillation cycle time is close to the

derivative time, reduce the derivative

time (b5-05).

• If the derivative time is set to 0.00 s and

oscillations are still a problem, reduce

the proportional gain (b5-02) or increase

the PID primary delay time (b5-08)

Response

Before adjustment

After adjustment

Time

n

b5-89: Sleep Method Selection

Determines how the drive sleeps and wakes-up when using PID.

No.

Name

Setting Range

Default

b5-89

Sleep Method Selection

0, 1

0

Setting 0: Standard
Setting 1: EZ Sleep/Wake-up

n

b5-90: EZ Sleep Unit

Sets the unit, range, and resolution of parameters b5-91 and b5-92.

No.

Name

Setting Range

Default

b5-90

EZ Sleep Unit

0, 1

<1>

0

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

Setting 0: Hz
Setting 1: RPM (number of motor poles must be entered)

n

b5-91: EZ Minimum Speed

Sets the PID minimum speed and integral lower limit.
The lower limit of the internal value is the higher of b5-34 and d2-02.

5.2 b: Application