No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U1-18

(61)

oPE Fault Parameter

Displays the parameter number that caused the oPEoo or Err (EEPROM

write error) error.

No signal output

available

U1-25

(4D)

Software Number (Flash) FLASH ID

No signal output

available

U1-26

(5B)

Software No. (ROM)

ROM ID

No signal output

available

U1-75

(851)

Time-Hour/Minute

Displays the current time (Hours and Minutes).

No signal output

available

U1-76

(852)

Date – Year

Displays the current year.

No signal output

available

U1-77

(853)

Date – Month/Day

Displays the current date (Month and Date).

No signal output

available

U1-78

(854)

Date – Week Day

Displays the current date of the week.

0: Sunday

1: Monday

2: Tuesday

3: Wednesday

4: Thursday

5: Friday

6: Saturday

No signal output

available

<1> The number of decimal places in the parameter value depends on the drive model.

Refer to Defaults by Drive Model on page 275

for details.

<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 208 V bypass drives. Double the value for 480 V bypass drives.

u

U2: Fault Trace

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U2-01

(80)

Current Fault

Displays the current fault.

No signal output

available

U2-02

(81)

Previous Fault

Displays the previous fault.

No signal output

available

U2-03

(82)

Frequency Reference at

Previous Fault

Displays the frequency reference at the previous fault.

No signal output

available

0.01 Hz

U2-04

(83)

Output Frequency at

Previous Fault

Displays the output frequency at the previous fault.

No signal output

available

0.01 Hz

U2-05

(84)

Output Current at Previous

Fault

Displays the output current at the previous fault.

No signal output

available

<1>

<2>

U2-07

(86)

Output Voltage at

Previous Fault

Displays the output voltage at the previous fault.

No signal output

available

0.1 Vac

U2-08

(87)

DC Bus Voltage at

Previous Fault

Displays the DC bus voltage at the previous fault.

No signal output

available

1 Vdc

U2-09

(88)

Output Power at Previous

Fault

Displays the output power at the previous fault.

No signal output

available

0.1 kW

U2-11

(8A)

Input Terminal Status at

Previous Fault

Displays the input terminal status at the previous fault. Displayed as in

U1-10.

No signal output

available

U2-12

(8B)

Output Terminal Status at

Previous Fault

Displays the output status at the previous fault. Displays the same status

displayed in U1-11.

No signal output

available

U2-13

(8C)

Drive Operation Status at

Previous Fault

Displays the operation status of the drive at the previous fault. Displays the

same status displayed in U1-12.

No signal output

available

U2-14

(8D)

Cumulative Operation

Time at Previous Fault

Displays the cumulative operation time at the previous fault.

No signal output

available

1 h

U2-15

(7E0)

Soft Starter Speed

Reference at Previous

Fault

Displays the speed reference for the soft starter at the previous fault.

No signal output

available

0.01 Hz

U2-16

(7E1)

Motor q-Axis Current at

Previous Fault

Displays the q-axis current for the motor at the previous fault.

No signal output

available

0.10%

B.13 U: Monitors

262

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual