Bypass fault numbers – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 363

Advertising
background image

Continue at Last Speed with Alarm
For this condition, Communication Fault Enable (BO 11) must be enabled and Cable Loss Speed (AO 22) should be set to a

value other than 0. An AL14 Serial Communications Alarm is shown.
Continue at Preset Speed with Alarm
In this mode, Cable Loss Timeout (AO 21) is set to the desired interval, Cable Loss Speed (AO 22) is set to the desired preset

speed and Z3–05 is set to “4”. If the time between messages exceeds the timeout interval, the drive speed command (AO 1)

is set to the Cable Loss Speed (AO 22) and the drive continues running at this new speed. Communication Fault Enable (BO

11) must be set to ‘On’.
Stop with Fault (FB14)
Communication Fault Enable (BO 11) must be set to ‘On’. In this mode, Cable Loss Timeout (AO 21) is set to the desired

interval and parameter F6-03 is set to a value of 0,1 or 2. If the time between messages exceeds the timeout interval, the drive

will declare an EF0 fault and the drive speed command (AO 1) will be set to 0. The stopping method is determined by the

setting of F6-03.
• F6–03 = 0 selects Ramp to Stop. The deceleration time or the slope of the ramp is determined by the setting of drive parameter

C1-02

• F6–03 = 1 selects Coast to Stop. The drive does not attempt to control the rate of deceleration.
• F6–03 = 2 selects Emergency or Fast Stop. The deceleration time is determined by the setting of drive parameter C1-09.

n

Bypass Fault Numbers

Table G.3 Fault Trace / History Register Contents

Fault Code

Fault Name

0002H

Undervoltage (Uv1)

0003H

Control Power Supply Undervoltage (Uv2)

0004H

Soft Charge Circuit Fault (Uv3)

0006H

Ground Fault (GF)

0007H

Overcurrent (oC)

0008H

Overvoltage (ov)

0009H

Heatsink Overheat (oH)

000AH

Heatsink Overheat (oH1)

000BH

Motor Overload (oL1)

000CH

Drive Overload (oL2)

000DH

Overtorque Detection 1 (oL3)

0010H

Braking Resistor Overheat (rH)

0011H

External Fault at Input Terminal S3 (EF3)

0012H

External Fault at Input Terminal S4 (EF4)

0013H

External Fault at Input Terminal S5 (EF5)

0014H

External Fault at Input Terminal S6 (EF6)

0015H

External Fault at Input Terminal S7 (EF7)

001BH

Input Phase Loss (PF)

001CH

Output Phase Loss (LF)

001DH

Motor Overheat (PTC input) (oH3)

001EH

Digital Operator Connection (oPr)

001FH

EEPROM Write Error (Err)

0020H

Motor Overheat (PTC input) (oH4)

0021H

MEMOBUS/Modbus Communication Error (CE)

0022H

Option Communication Error (bUS)

0027H

Option External Fault (EF0)

0028H

PI Feedback Loss (FbL)

0029H

Undertorque Detection 1 (UL3)

002BH

High Slip Braking Overload (oL7)

0030H

Hardware Fault (including oFx)

0036H

Output Current Imbalance (LF2)

Fault Code

Fault Name

0037H

Pullout Detection (Sto)

003BH

Too Many Speed Search Restarts (SEr)

0041H

PI Feedback Loss (FbH)

0042H

External Fault 1, Input Terminal S1 (EF1)

0043H

External Fault 2, Input Terminal S2 (EF2)

0046H

Current Offset Fault (CoF)

0047H

PLC Detection Error 1 (PE1)

0048H

PLC Detection Error 2 (PE2)

004DH

Output Voltage Detection Fault (voF)

0052H

Node Setup Fault (nSE)

005AH

Motor Underload Protection (UL6)

0083H

A/D Conversion Error (CPF02)

0084H

PWM Data Fault (CPF03)

0087H

EEPROM Memory Data Error (CPF06)

0088H

Terminal Board Connection Error (CPF07)

0089H

EEPROM Serial Communication Fault (CPF08)

008CH

RAM Fault (CPF11)

008DH

Flash Memory Circuit Exception (CPF12)

008EH

Watchdog Circuit Exception (CPF13)

008FH

Control Circuit Fault (CPF14)

0091H

Clock Fault (CPF16)

0092H

Timing Fault (CPF17)

0093H

Control Circuit Fault (CPF18)

0094H

Control Circuit Fault (CPF19)

0095H

Hardware Fault at Power Up (CPF20)

0096H

Hardware Fault at Communication Start Up (CPF21)

0097H

A/D Conversion Fault (CPF22)

0098H

PWM Feedback Fault (CPF23)

0099H

Drive Unit Signal Fault (CPF24)

009AH

Terminal Board is Not Properly Connected. (CPF25)

009BH

ASIC BB Circuit Error (CPF26)

G.4 Bypass Operations by N2

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

363

G

Metasys N2 Network Protocol