Starting auto-tuning, T1-01: auto-tuning mode selection, T1-02: motor rated power – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 79: T1-03: motor rated voltage

Advertising
background image

n

Starting Auto-Tuning

WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or

serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.

WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the

motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.

NOTICE: Rotational Auto-Tuning will not function properly if the motor cannot spin freely. Failure to comply could result in improper operation

of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.

Enter the required information from the motor nameplate. Press

to proceed to the Auto-Tuning start display.

Note:

These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.

Step

Display/Result

1. After entering the data listed on the motor nameplate, press

to confirm.

DRV-OFF

0.00 Hz/ 0.00A

Tuning Ready?

Auto-Tuning

DATA

ESC

Press HAND Key

2. Press

HAND

to activate Auto-Tuning.

flashes. The drive begins by injecting current

into the motor for about 1 min, and then starts to rotate the motor.

DRV-OFF

0.00 Hz/ 0.00A

Tuning Ready?

Tune Proceeding

Press HAND Key

3. Auto-Tuning finishes in approximately one to two minutes.

MODE

Tune Successful

End

RESET

u

T1: Parameter Settings during Induction Motor Auto-Tuning

The T1-oo parameters set the Auto-Tuning input data for induction motor tuning.

Note:

For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is complete, change

E1-04, Maximum Output Frequency, to the desired value.

n

T1-01: Auto-Tuning Mode Selection

Sets the type of Auto-Tuning to be used. Refer to the User Manual packaged with the drive for details on the different types

of Auto-Tuning.

No.

Name

Setting Range

Default

T1-01

Auto-Tuning Mode Selection

2, 3 (V/f)

2 (V/f)

Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotational Auto-Tuning for V/f Control Energy Saving

n

T1-02: Motor Rated Power

Sets the motor rated power according to the motor nameplate value.

Note:

Use the following formula to convert HP to kW: kW = HP x 0.746.

No.

Name

Setting Range

Default

T1-02

Motor Rated Power

0.00 to 650.00 kW

Determined by o2-04

n

T1-03: Motor Rated Voltage

Sets the motor rated voltage according to the motor nameplate value. Enter the voltage base speed when the motor operates

above base speed. Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03.

No.

Name

Setting Range

Default

T1-03

Motor Rated Voltage

0.0 to 255.0 V

<1>

200.0 V

<1>

<1> Values shown are specific to 200 V Class. Double the value for 400 V Class.

4.7 Auto-Tuning

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

79

4

Start-Up Programming & Operation

Advertising