5 e: motor parameters – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 110

Advertising
background image

Setting

Specification

Characteristic

Application

8

50 Hz, High starting torque 1

High starting torque

Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.

9

50 Hz, High starting torque 2

A

60 Hz, High starting torque 1

B

60 Hz, High starting torque 2

C

90 Hz (with 60 Hz base)

Constant output

Output voltage is constant when operating at greater than

60 Hz.

D

120 Hz (with 60 Hz base)

E

180 Hz (with 60 Hz base)

F

<1>

60 Hz

Variable torque

Used for variable torque applications. The default setting is

the same as V/f pattern Setting 7.

<1> Setting F enables a custom V/f pattern by changing parameters E1-05. When the bypass is shipped, the default values for parameter E1-05 is are

equal to predefined V/f pattern 1.

The following tables show details on predefined V/f patterns.

Predefined V/f Patterns for Models D002 to D024 and B001 to B011

The voltage values in the graphs for settings 0 to E apply to applications with 200 V motors. Double the voltage values for

400 V motors. The voltage values in settings 0 to E do not apply to 208, 230, or 460 V motor applications.

Table 5.10 Constant Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

9

200

1.3 2.5

50

15

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

60

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 5.11 Variable Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

8

200

1.3

25

50

35

V

oltage (V)

Frequency (Hz)

0

9

200

1.3

25

50

50

V

oltage (V)

Frequency (Hz)

0

8

200

1.5

30

60

35

V

oltage (V)

Frequency (Hz)

0

9

200

1.5

30

60

50

V

oltage (V)

Frequency (Hz)

Table 5.12 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

11

200

1.3 2.5

50

19

V

oltage (V)

Frequency (Hz)

0

13

200

1.3 2.5

50

24

V

oltage (V)

Frequency (Hz)

0

11

200

1.5 3

60

19

V

oltage (V)

Frequency (Hz)

0

15

200

1.5 3

60

24

V

oltage (V)

Frequency (Hz)

Table 5.13 Rated Output Operation, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

9

15

200

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

10.2

17.3

230

1.5 3

60

V

oltage (V)

Frequency (Hz)

5.5 E: Motor Parameters

110

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual