H5: memobus/modbus serial communication – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 249

No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H4-05
(421)
Multi-Function Analog
Output Terminal AM
Gain
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of
the selected monitor value.
Default: 50.0%
Min.: -999.9
Max.: 999.9
H4-06
(422)
Multi-Function Analog
Output Terminal AM
Bias
Terminal AM Bias
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
H4-07
(423)
Multi-Function Analog
Output Terminal FM
Signal Level Selection
Term FM Lvl Sel
0: 0 to 10 V
1: -10 to +10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
H4-08
(424)
Multi-Function Analog
Output Terminal AM
Signal Level Selection
Term AM Lvl Sel
0: 0 to 10 V
1: -10 to +10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
u
H5: MEMOBUS/Modbus Serial Communication
No.
(Addr.
Hex)
Name
Description
Values
Page
H5-04
(428)
Stopping Method after
Communication Error (CE)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm only
Default: 3
Range: 0 to 3
B.8 H Parameters: Multi-Function Terminals
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
249
B
Parameter List