H5: memobus/modbus serial communication – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 249

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H4-05

(421)

Multi-Function Analog

Output Terminal AM

Gain

Terminal AM Gain

Sets the signal level at terminal AM that is equal to 100% of

the selected monitor value.

Default: 50.0%

Min.: -999.9

Max.: 999.9

123

H4-06

(422)

Multi-Function Analog

Output Terminal AM

Bias

Terminal AM Bias

Sets the signal level at terminal AM that is equal to 0% of the

selected monitor value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

123

H4-07

(423)

Multi-Function Analog

Output Terminal FM

Signal Level Selection

Term FM Lvl Sel

0: 0 to 10 V

1: -10 to +10 V

2: 4 to 20 mA

Default: 0

Range: 0 to 2

124

H4-08

(424)

Multi-Function Analog

Output Terminal AM

Signal Level Selection

Term AM Lvl Sel

0: 0 to 10 V

1: -10 to +10 V

2: 4 to 20 mA

Default: 0

Range: 0 to 2

124

u

H5: MEMOBUS/Modbus Serial Communication

No.

(Addr.

Hex)

Name

Description

Values

Page

H5-04

(428)

Stopping Method after

Communication Error (CE)

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm only

Default: 3

Range: 0 to 3

125

B.8 H Parameters: Multi-Function Terminals

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

249

B

Parameter List