No.

(Addr.

Hex)

Name

Description

Values

Page

b5-46

(165)

PID Units Selection

Sets the display units for parameter b5-19, and monitors U5-01, U5-04 and

U5-99

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

15: “Hg (Inches of Mercury)

25: No unit

Default: 0

Range: 0 to 15; 25

100

b5-47

(17D)

Reverse Operation Selection

2 by PID Output

0: Zero limit when PID output is a negative value.

1: Reverse operation when PID output is a negative value

(Zero limit if the reverse operation is prohibited by b1-04).

Default: 1

Range: 0, 1

100

b5-89

(B89)

Sleep Method Selection

Determines how the drive sleeps and wakes-up when using PID.

0: Standard

1: EZ Sleep/Wake-up

Default: 0

Range: 0, 1

101

b5-90

(B90)

<2>

EZ Sleep Unit

Sets the unit, range, and resolution of parameters b5-91 and b5-92.

0: Hz

1: RPM (number of motor poles must be entered)

Default: 0

Range: 0, 1

101

b5-91

(B91)

<2>

EZ Minimum Speed

Sets the PID minimum speed and integral lower limit.

The internal value is lower limited to the higher setting between b5-34 and

d2-02.

Default: 0.0 Hz

Range: 0.0 to

400.0 Hz
or 0 to 24000 RPM

<3>

101

b5-92

(B92)

<2>

EZ Sleep Level

The drive will go to sleep when the drive output frequency (or speed) is at or

below this level for the time set in b5-93.

This parameter is internally lower limited to b5-91 (EZ Min Speed) + 1Hz.

Default: 0.0 Hz

Range: 0.0 to

400.0 Hz
or 0 to 24000 RPM

<3>

102

b5-93

(B93)

<2>

EZ Sleep Time

The drive will go to sleep when the drive output frequency is at or below the

level set to b5-92 for the time set in this parameter.

Default: 5.0 s

Min.: 0.0

Max.: 1000.0

102

b5-94

(B94)

<2>

EZ Wake-up Level

When b5-95 is set to 0 (Absolute), the drive wakes-up when the PID Feedback

(H3-oo = 20) drops below this level for the time set in b5-96.

For reverse-acting, the PID Feedback must be above this level for the time set

in b5-96.

When b5-95 is set to 1 (Setpoint Delta), the drive wakes-up when the PID

Feedback (H3-oo = 20) drops below the PID Setpoint minus this level (for

normal acting PID) for the time set in b5-96.

For reverse-acting, Wake-up level is PID Setpoint plus this level. The PID

Feedback must be above the wake-up level for the time set in b5-96.

Default: 0.00%

Min.: 0.00

Max.: 600.00

102

b5-95

(B95)

<2>

EZ Wake-up Mode

Sets how the wake-up level is determined.

0: Absolute

1: Setpoint Delta

Default: 0

Range: 0, 1

102

b5-96

(B96)

<2>

EZ Wake-up Time

The drive will wake up when the PID Feedback drops below the b5-94, EZ

Wake-up Level for the time set in this parameter.

Default: 1.0 s

Min.: 0.0

Max.: 1000.0

102

<2> Parameter is only effective when EZ Sleep is enabled by setting b5-89 to 1.
<3> Unit, range and resolution is determined by b5-90. Changing b5-90 will not automatically update the value of this parameter.

B.3 b: Application

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

241

B

Parameter List