13 z: bypass parameters – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 156

VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
2
t
1
t
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 10.0 sec
Z1-15 Interlck Wait Tm
t3
FAULT: FB02 BAS Ilock Open
Figure 5.46 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
t1
t2
t3
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 1 (Enable)
Z1-14 Run Delay Fref = 30.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)
Z1-14 Run Delay Fref
t4
Figure 5.47 Run Delay with Preset Speed Example: Preset Speed
5.13 Z: Bypass Parameters
156
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual