n3-13: Overexcitation Deceleration Gain

Multiplies a gain to the V/f pattern output value during Overexcitation Deceleration to determine the level of overexcitation.

The drive returns to the normal V/f value after the motor has stopped or when it is accelerating to the frequency reference.

No.

Name

Setting Range

Default

n3-13

Overexcitation Deceleration Gain

1.00 to 1.40

1.10

The optimum setting for n3-13 depends on the motor flux saturation characteristics.
• Gradually increase the gain to 1.25 or 1.30 to improve the braking power of Overexcitation Deceleration.
• Lower n3-13 when flux saturation characteristics cause overcurrent. A high setting sometimes causes overcurrent (oC),

motor overload (oL1), or drive overload (oL2). Lowering n3-21 can also help remedy these problems.

5.9 n: Special Adjustments

140

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual