Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 265

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U4-06

(07D6)

Soft Charge Bypass Relay

Maintenance

Displays the soft charge bypass relay maintenance time as a percentage of

its estimated performance life. Parameter o4-07 can be used to reset this

monitor.

No signal output

available

1%

U4-07

(07D7)

IGBT Maintenance

Displays IGBT usage time as a percentage of the expected performance

life. Parameter o4-09 can be used to reset this monitor.

No signal output

available

1%

U4-08

(68)

Heatsink Temperature

Displays the heatsink temperature.

10 V: 100 °C

1 °C

U4-09

(5E)

LED Check

Lights all segments of the LED to verify that the display is working

properly.

No signal output

available

U4-10

(5C)

kWh, Lower 4 Digits

Monitors the drive output power. The value is shown as a 9-digit number

displayed across two monitor parameters, U4-10 and U4-11.

Example:

12345678.9 kWh is displayed as:

U4-10: 678.9 kWh

U4-11: 12345 MWh

No signal output

available

1 kWh

U4-11

(5D)

kWh, Upper 5 Digits

No signal output

available

1 MWh

U4-13

(7CF)

Peak Hold Current

Displays the highest current value that occurred during run.

No signal output

available

0.01 A

<1>

U4-14

(7D0)

Peak Hold Output

Frequency

Displays the output frequency when the current value shown in U4-13

occurred.

No signal output

available

0.01 Hz

U4-16

(7D8)

Motor Overload Estimate

(oL1)

Shows the value of the motor overload detection accumulator. 100% is

equal to the oL1 detection level.

10 V: 100%

0.1%

U4-18

(7DA)

Frequency Reference

Source Selection

Displays the source for the frequency reference as XY-nn.

X: indicates which reference is used:

0 = OFF

1 = AUTO

2 = HAND

Y-nn: indicates the reference source

0-01 = HOA keypad

1-00 = Analog (not assigned)

1-01 = Analog (terminal A1)

1-02 = Analog (terminal A2)

1-03 = Analog (terminal A3)

2-02 to 17 = Multi-step speed (d1-02 to 17)

3-01 = MEMOBUS/Modbus communications

4-01 = Communication option card

9-01 = Up/Down

No signal output

available

U4-19

(7DB)

Frequency Reference from

MEMOBUS/Modbus

Comm.

Displays the frequency reference provided by MEMOBUS/Modbus

(decimal).

No signal output

available

0.01%

U4-20

(7DC)

Option Frequency

Reference

Displays the frequency reference input by an option card (decimal).

No signal output

available

U4-21

(7DD)

Run Command Source

Selection

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

0 = OFF

1 = AUTO

2 = HAND

Y: Input power supply data

0 = HOA keypad

1 = External terminals

3 = BACnet or MEMOBUS/Modbus communications

4 = Communication option card

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to REMOTE

operation

03: Waiting for soft charge bypass contactor after power up (Uv or Uv1

flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, HOA keypad)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during baseblock

09: Waiting for Enter command

No signal output

available

B.13 U: Monitors

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

265

B

Parameter List