Sequence Timers 2 to 4

These timers operate identically to Sequence Timer 1. Parameters S2-06 to S2-20 configure Sequence Timers 2 to 4.

Priority

If multiple sequence timers overlap, the timer with the lowest number has priority.
Sequence Timer 1 = highest priority
Sequence Timer 4 = lowest priority

n

S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time

Sets the start times for timers 1 to 4. The values must be set less than or equal to S2-02/S2-07/S2-12/S2-17.

No.

Name

Setting Range

Default

S2-01

Sequence Timer 1 Start Time

00:00 to 24:00

00:00

S2-06

Sequence Timer 2 Start Time

00:00 to 24:00

00:00

S2-11

Sequence Timer 3 Start Time

00:00 to 24:00

00:00

S2-16

Sequence Timer 4 Start Time

00:00 to 24:00

00:00

n

S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time

Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.

No.

Name

Setting Range

Default

S2-02

Sequence Timer 1 Stop Time

00:00 to 24:00

00:00

S2-07

Sequence Timer 2 Stop Time

00:00 to 24:00

00:00

S2-12

Sequence Timer 3 Stop Time

00:00 to 24:00

00:00

S2-17

Sequence Timer 4 Stop Time

00:00 to 24:00

00:00

n

S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection

Sets the days for which sequence timers 1 to 4 are active.

No.

Name

Setting Range

Default

S2-03

Sequence Timer 1 Day Selection

0 to 10

0

S2-08

Sequence Timer 2 Day Selection

0 to 10

0

S2-13

Sequence Timer 3 Day Selection

0 to 10

0

S2-18

Sequence Timer 4 Day Selection

0 to 10

0

Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday

n

S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection

Sets the action that occurs when sequence timers 1 to 4 are active.

No.

Name

Setting Range

Default

S2-04

Sequence Timer 1 Selection

0 to 2

0

S2-09

Sequence Timer 2 Selection

0 to 2

0

S2-14

Sequence Timer 3 Selection

0 to 2

0

5.11 S: Special Parameters