Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 299

Advertising
background image

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BV20

Drive OverLoad

0021H:bit 2

OL2

OFF

R

BV21

Drive OverHeat

0021H:bit 3

OH1-OH2

OFF

R

BV22

Fuse Blown

0021H:bit 5

PUF

OFF

R

BV23

PI Feedback Loss

0021H:bit 6

FBL

OFF

R

BV24

External Fault

0021H:bit 7

EF0-EF

OFF

R

BV25

Hardware Error

0021H:bit 8

CPF

OFF

R

BV26

Mtr Ovrld-OvrTorque

0021H:bit 9

OL1-OL3

OFF

R

BV27

OverSpeed

0021H:bit 10

OS-DEV

OFF

R

BV28

Main Ckt UnderVoltage

0021H:bit 11

UV

OFF

R

BV29

MCU Cntl Pwr Sy Err

0021H:bit 12

UV1-2-3

OFF

R

BV30

Output Phase Loss

0021H:bit 13

LF

OFF

R

BV31

Communication Error

0021H:bit 14

CE

OFF

R

BV32

Operator Disconnect

0021H:bit 15

OPR

OFF

R

BV33

Operating

002CH:bit 0

OPERATING

OFF

R

BV34

Zero Speed

002CH:bit 1

ON

OFF

R

BV35

Frequency Agree

002CH:bit 2

ON

OFF

R

BV36

Desired Freq Agree

002CH:bit 3

ON

OFF

R

BV37

Frequency Detect 1

002CH:bit 4

ON

OFF

R

BV38

Frequency Detect 2

002CH:bit 5

ON

OFF

R

BV39

Drv Startup Complete

002CH:bit 6

ON

OFF

R

BV40

Low Voltage Detect

002CH:bit 7

ON

OFF

R

BV41

Base Block

002CH:bit 8

ON

OFF

R

BV42

Frequency Ref Mode

8785H:bit 8

COM

LOCAL

R

BV43

Run Command Mode

8485H:bit 9

COM

LOCAL

R

BV44

Over Torque Detect

002CH:bit 11

ON

OFF

R

BV45

Frequency Ref Lost

002CH:bit 12

ON

OFF

R

BV46

Retry Error

002CH:bit 13

ON

OFF

R

BV47

Modbus Comms Error

002CH:bit 14

ON

OFF

R

BV48

Modbus Timeout Error

002CH:bit 15

ON

OFF

R

BV49

CRC Error

003DH:bit 0

ON

OFF

R

BV50

Invalid Data Length

003DH:bit 1

ON

OFF

R

BV51

Parity Error

003DH:bit 3

ON

OFF

R

BV52

Overrun Error

003DH:bit 4

ON

OFF

R

BV53

Framing Error

003DH:bit 5

ON

OFF

R

BV54

Timeout Error

003DH:bit 6

ON

OFF

R

BV55

<1>

Parameter Accept

0910H:bit 0

ON

OFF

W

BV56

<1>

Parameter Enter

0900H:bit 0

ON

OFF

W

BV57

Drive Comms Error

002CH:bit 15

ON

OFF

R

BV58

BYP Run Fwd CMD

8400H: bit 0

ON

OFF

C

BV59

BYP Run Rev CMD

8400H: bit 1

ON

OFF

C

BV60

Not Used BV60

ON

OFF

R

BV61

BYP Xfer to BYP CMD

8400H: bit 3

ON

OFF

C

BV62

BYP Smok Prg BYP CMD

8400H: bit 4

ON

OFF

C

BV63

BYP Smok Prg DRV CMD

8400H: bit 5

ON

OFF

C

BV64

BYP Mtr OR Sel CMD

8400H: bit 6

ON

OFF

C

BV65

BYP Mtr AND Sel CMD

8400H: bit 7

ON

OFF

C

BV66

BYP Drive Select CMD

8400H: bit 9

ON

OFF

C

BV67

BYP Auto Select CMD

8400H: bit 10

ON

OFF

C

BV68

Not Used BV68

8400H: bit 11

ON

OFF

C

C.6 BACnet Objects Supported

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

299

C

BACnet Communications

Advertising