5.13 Z: Bypass Parameters

Z parameters control bypass-specific functions.

u

Z1: Bypass Control System

n

Z1-01: Initialize

Sets parameters to default values.

No.

Name

Setting Range

Default

Z1-01

Initialize

0 to 3; 8008 to 8011

0

Setting 0: No Initialize
Setting 1: Set all parameters to default values
Setting 2: Set only Bypass Controller parameters to default values
Setting 3: Set only Drive Controller parameters to default values
Setting 8008: Pump

Application Preset for pump applications.

Refer to Application Selection on page 75

for a list of parameters and default values

for this Application Preset.

Setting 8009: Pump w/ PI

Application Preset for pump applications.

Refer to Application Selection on page 75

for a list of parameters and default values

for this Application Preset.

Setting 8010: Fan

Application Preset for pump applications.

Refer to Application Selection on page 75

for a list of parameters and default values

for this Application Preset.

Setting 8011: Fan w/ PI

Application Preset for pump applications.

Refer to Application Selection on page 75

for a list of parameters and default values

for this Application Preset.

n

Z1-02: Password

Allows and restricts access to all parameters. Setting this value equal to the value in Z1-03 toggles access to all parameter

settings, except Z1-02. If the value entered to Z1-02 matches the value entered to Z1-03, the access to all parameters is denied

or granted.

No.

Name

Setting Range

Default

Z1-02

Password

n

Z1-03: Password Change

The value entered to this parameter is the password.

No.

Name

Setting Range

Default

Z1-03

Password Change

0 to 9999

0

n

Z1-05: Auto Transfer to Bypass Upon Drive Fault

Switches operation to Bypass mode when the drive is running and a drive fault occurs. When the fault is cleared, operation

will switch back to Drive mode

No.

Name

Setting Range

Default

Z1-05

Auto Transfer to Bypass Upon Drive Fault

0, 1

0

Setting 0: Disable
Setting 1: Enable

5.13 Z: Bypass Parameters

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

151