Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 102

Advertising
background image

No.

Name

Setting Range

Default

b5-91

EZ Minimum Speed

0.0 to 400.0 Hz

<1>

or 0 to 24000 RPM

0.0

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

n

b5-92: EZ Sleep Level

When the drive output frequency (or speed) is at or below this level for the time set in b5-93, the drive will go to sleep.
The internal lower limit of this parameter is b5-91 (EZ Min Speed) + 1 Hz.

No.

Name

Setting Range

Default

b5-92

EZ Sleep Level

0.0 to 400.0 Hz

<1>

or 0 to 24000 RPM

0.0

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

n

b5-93: EZ Sleep Time

The drive will go to sleep when the drive output frequency is at or below the level set to b5-92 for the time set in this parameter.

No.

Name

Setting Range

Default

b5-93

EZ Sleep Tim

0.0 to 10000.0

<1>

5.0 s

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

n

b5-94: EZ Wake-up Level

If b5-95 is set to 0 (Absolute), the drive wakes-up when the PID Feedback (H3-oo = 20) drops below this level for the time

set in b5-96. For reverse-acting, the PID Feedback has to be above this level for the time set in b5-96.
If b5-95 is set to 1 (Setpoint Delta), the drive wakes-up when the PID Feedback (H3-oo = 20) drops below the PID Setpoint

minus this level (for normal acting PID) for the time set in b5-96. For reverse-acting, Wake-up level is PID Setpoint plus this

level. The PID Feedback has to be above the wake-up level for the time set in b5-96.

No.

Name

Setting Range

Default

b5-94

EZ Wake-up Level

0.00 to 600.00%

<1>

0.00

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

n

b5-95: EZ Wake-up Mode

Sets how the wake-up level is determined.

No.

Name

Setting Range

Default

b5-95

EZ Wake-up Mode

0, 1

<1>

0

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

Setting 0: Absolute
Setting 1: Setpoint Data

n

b5-96: EZ Wake-up Time

The drive will wake up when the PID Feedback drops below the b5–94, EZ Wake-up Level for the time set in this parameter.

No.

Name

Setting Range

Default

b5-96

EZ Wake-up Time

0.0 to 1000.0

<1>

1.0 s

<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically

update the value of this parameter.

5.2 b: Application

102

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual