L6-02: torque detection level 1, L6-03: torque detection time 1, 8 l: protection functions – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 135

Advertising
background image

Motor current / torque

L6-02

10 % hysteresis

Torque detection 1 (NO)

or

Torque detection 2 (NO)

L6-03

ON

L6-03

10 % hysteresis

ON

Figure 5.37 Overtorque Detection Operation

Motor current / torque

L6-02

10 % hysteresis

Torque detection 1 (NO)

or

Torque detection 2 (NO)

L6-03

ON

L6-03

ON

Figure 5.38 Undertorque Detection Operation

Note:

1. The torque detection function uses a hysteresis of 10% of the drive rated output current and motor rated torque.
2. The level is set as a percentage of the drive rated output current.

n

L6-02: Torque Detection Level 1

Sets the detection levels for torque detection function 1 as a percentage of the drive rated output current.

No.

Name

Setting Range

Default

L6-02

Torque Detection Level 1

0 to 300%

15%

Note:

The torque detection level 1 (L6-02) can also be supplied by an analog input terminal set to H3-oo = 7. Here, the analog value has priority

and the setting in L6-02 is disregarded.

n

L6-03: Torque Detection Time 1

Determines the time required to trigger an alarm or fault after exceeding the level in L6-02.

No.

Name

Setting Range

Default

L6-03

Torque Detection Time 1

0.0 to 10.0 s

10.0 s

5.8 L: Protection Functions

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

135

5

Programming