Switches and jumpers on the terminal board, Figure 3.6, 4 control circuit wiring – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 51

Advertising
background image

A

E

B

C

D

A – Drive side
B – Connect shield to ground terminal

of drive.

C – Insulation

D – Control device side
E – Shield sheath (insulate with tape)
F – Shield

Figure 3.6 Preparing the Ends of Shielded Cables

NOTICE: The analog signal wiring between the drive and the operator station or peripheral equipment should not exceed 50 meters when

using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.

u

Switches and Jumpers on the Terminal Board

The terminal board is equipped with several switches used to adapt the drive I/Os to the external control signals.

Figure 3.7

shows the location of these switches.

Refer to Bypass and Drive Control I/O Connections on page 52

for setting instructions.

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

Selection

V

AM

FM

I

Jumper S5

Terminal AM/FM Signal

DIP Switch S2

RS-422/485 Termination

Resistor

Off

On

Jumper S1

A1/A2/A3 Volt/Curr.

Selection

V

I

A1 A2 A3

Figure 3.7 Locations of Jumpers and Switches on the Terminal Board

3.4 Control Circuit Wiring

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

51

3

Electrical Installation

Advertising