Z1-27: Phase Loss Brownout Voltage Level

Sets the brownout condition voltage level.

No.

Name

Setting Range

Default

Z1-27

Phase Loss Brownout Voltage Level

0 to 150 V

98 V

n

Z1-28: Phase Loss Brownout Detection Time

Sets the time that the input voltage is continuously measured to be below the Brownout Voltage level before declaring a

brownout fault.

No.

Name

Setting Range

Default

Z1-28

Phase Loss Brownout Detection Time

0.0 to 300.0 s

3.0 s

n

Z1-29: Phase Loss Blackout Voltage Level

Sets the voltage level below which is considered a blackout condition.

No.

Name

Setting Range

Default

Z1-29

Phase Loss Blackout Voltage Level

0 to 150 V0

0 V

n

Z1-30: EF0 Fault Delay Time

Sets the time between declaring a drive fault and opening the drive and bypass contactors.

No.

Name

Setting Range

Default

Z1-30

EF0 Fault Delay Time

0.0 to 300.0 s

1.0 s

n

Z1-31: Loss of Load Detection Enable

No.

Name

Setting Range

Default

Z1-31

Loss of Load Detection Enable

0 to 2

0

Setting 0: Disable
Setting 1: Enable and Declare Fault
Setting 2: Enable and Alarm Only

n

Z1-32: Loss of Load Drive Frequency

Sets the value to which the drive output frequency must be equal to or greater than for the drive to detect a loss of load.

No.

Name

Setting Range

Default

Z1-32

Loss of Load Drive Frequency

0.0 to 60.0 Hz

<1>

60.0 Hz

<1>

<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.

n

Z1-33: Loss of Load Drive Output Current

Sets the value to which the drive output current must be equal to or less than for the drive to detect a loss of load.

No.

Name

Setting Range

Default

Z1-33

Loss of Load Drive Output Current

0.0 to 999.9 A

0.0 A

n

Z1-34: Loss of Load Drive Time

While in Drive mode, the Loss of Load detection conditions must be met for the length of time entered here before detecting

a loss of load.

No.

Name

Setting Range

Default

Z1-34

Loss of Load Drive Time

0.0 to 300.0 s

1.0 s

n

Z1-35: Loss of Load Bypass Output Current

The motor current must be equal to or less than this value to detect a loss of load.