Inspection Area
Inspection Points
Corrective Action
Checked
Heatsink
Inspect for dust or other foreign material collected on the
surface.
Remove foreign particles and dust with a vacuum
cleaner to avoid touching parts.
Air Duct
Inspect air intake and exhaust openings. They must be
free from obstruction and properly installed.
• Visually inspect the area.
• Clear obstructions and clean air duct as required.
Display Periodic Inspection
HOA Keypad
• Make sure data appears on the display properly.
• Inspect for dust or other foreign material that may have
collected on surrounding components.
• Contact the nearest sales office if there is any
trouble with the display or keypad.
• Clean the HOA keypad