Step

Display/Result

Motor Rotation in Bypass Mode

11. Press

F2

to toggle to the Bypass Mode.

The keypad display should show BYP–OFF if the device is ready for Bypass operation.

BYP-OFF

U1-01=

0

0.0Hz

Frequency Ref

U1-02= 0.00Hz
U1-03= 0.0A

LSEQ

LREF

RLY

DRV/BYP

12. Bump the motor by pressing

HAND

then quickly pressing

OFF

. Ensure the motor is

rotating in the correct direction and that no faults or alarms occur.

Motor

Forward

13.

If the direction of motor rotation is incorrect, press

OFF

to stop the motor. The HAND

light turns OFF and the motor coasts to stop.

Skip to step 15 if the direction of motor rotation is correct.

F2

F1

ESC

M

M

AUTO

OFF

ENTER

RESET

ALM

DIGITAL OPERATOR JVOP-183

HAND

On

Off

HAND

HAND

DRV-OFF

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

Freq Ref (AUTO)

BYPASS

LSEQ

LREF

14.

Turn off the power to the P1000 Bypass.

WARNING! Electrical Shock Hazard. Do not touch any terminals before the

capacitors have fully discharged. Failure to comply could result in death or serious

injury. Before servicing, disconnect all power to the equipment. The internal

capacitor remains charged even after the power supply is turned off. The charge

indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent

electric shock, wait for at least the time specified on the warning label, once all

indicators are OFF, measure for unsafe voltages to confirm the drive is safe prior

to servicing.

Switch the wires for L1 and L2 on the bypass input circuit breaker. Re-tighten the terminal

lugs and reapply power.

15.

Run the motor in Bypass Mode using

HAND

and check the motor current using UB-01.

Then measure the output voltage (Line-to-Line and Line-to-Ground) using a multimeter

and record the values for future reference.

BYP-RUN BYPASS

UB-01=

0

2.5A

Monitor Menu

UB-02=10000110
UB-03=10000110

LSEQ

LREF

RLY

DRV/BYP

16. The P1000 Bypass should operate normally. Press

OFF

to stop the motor. The HAND

light is OFF and the motor coasts to stop.

4.5 Start-Up Procedure

74

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual