Type

Signal Name

Description

Specification

Digital Outputs

120 Vac

DO-1

Digital Output 1

(Factory use only) 120 Vac, 66 VA sealed, 1650 inrush

DO-2

Digital Output 2

DO-3

Digital Output 3

DO-4

Digital Output 4

DO-5

Digital Output 5

Digital Outputs

DO-6

Digital Output 6

Relay, dry contact, form C, 30 Vdc or 120 Vac,

DO-6 (factory use only), 3.7 Amp 360 VA,

DO-7 to DO-10 for customer use, 2 Amp

DO-7

Digital Output 7

DO-8

Digital Output 8

DO-9

Digital Output 9

DO-10

Digital Output 10

Table 3.4

lists the available control circuit input terminals on the drive. Text in parenthesis indicates the default setting for

each multi-function input.
The drive control circuit terminals are arranged as shown in

Figure 3.3

.

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

Figure 3.3 Drive Control Circuit Terminal Board Arrangement

Table 3.4 Drive Control Circuit Terminal Board A1

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Frequency

Reference

Inputs

+V

Power supply for analog inputs

10.5 Vdc (maximum allowable current 20 mA)

152

A1

Multi-function analog input 1

(Frequency reference bias)

• 0 to 10 Vdc/100% (input impedance: 20 kΩ)
• 4 to 20 mA/100%, 0 to 20 mA/100% (input impedance: 250 Ω)
• Voltage or current input must be selected by Jumper S1 and H3-01.

117

152

A2

Multi-function analog input 2

(Frequency reference bias)

• 0 to 10 Vdc/100% (input impedance: 20 kΩ)
• 4 to 20 mA/100%, 0 to 20 mA/100% (input impedance: 250 Ω)
• Voltage or current input must be selected by Jumper S1 and H3-09.

119

152

152

A3

Multi-function analog input 3

(Auxiliary frequency reference 1)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-05.

152

AC

Frequency reference common

0 V

152

FE

Ground for shielded lines and option cards

u

Bypass Analog Outputs

There are two analog outputs that can be configured for a signal level of 0 to 10 Vdc or 4 to 20 mA. The signal level is controlled

by the position of jumpers J2 and J3 on Control PCB A2 and by the values set to drive parameters H4-07 and H4-08.

3.4 Control Circuit Wiring

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

47

3

Electrical Installation